beautypg.com

Caution, Water damage hazard – American Water Heater HCG3 130T 300 User Manual

Page 40

background image

40

t&p ValVe discharge pipe

Explosion Hazard

Temperature-Pressure Relief Valve

must comply with ANSI Z21.22-

CSA 4.4 and ASME code.

Properly sized temperature-

pressure relief valve must be

installed in opening provided.

Can result in overheating and

excessive tank pressure.

Can cause serious injury or death.

This water heater is provided with a properly rated/sized and

certified combination temperature - pressure (T&P) relief valve

by the manufacturer. See Temperature-Pressure Relief Valve on

page 15 for information on replacement and other requirements.

Water Damage Hazard

Temperature-Pressure Relief Valve discharge

pipe must terminate at adequate drain.

CAUTION

Install a discharge pipe between the T&P valve discharge opening

and a suitable floor drain. Do not connect discharge piping

directly to the drain unless a 6” (15.2 cm) air gap is provided.

To prevent bodily injury, hazard to life, or property damage, the

relief valve must be allowed to discharge water in adequate

quantities should circumstances demand. If the discharge pipe is

not connected to a drain or other suitable means, the water flow

may cause property damage.
t&p Valve discharge pipe requirements:

• Shall not be smaller in size than the outlet pipe size of the

valve, or have any reducing couplings or other restrictions.

• Shall not be plugged or blocked.
• Shall not be exposed to freezing temperatures.
• Shall be of material listed for hot water distribution.
• Shall be installed so as to allow complete drainage of both

the Temperature-Pressure Relief Valve and the discharge

pipe.

• Must terminate a maximum of six inches above a floor

drain or external to the building. In cold climates, it is

recommended that the discharge pipe be terminated at an

adequate drain inside the building.

• Shall not have any valve or other obstruction between the

relief valve and the drain.

water line connections

The water piping installation must conform to these instructions

and to all local and national code authority having jurisdiction.

Good practice requires that all heavy piping be supported.
Read and observe all requirements in the following sections

before installation of the water piping begins:
1. Mixing Valves on page 14.
2. Dishwashing Machines on page 14.
3. Temperature-Pressure Relief Valve on page 15.
4. Closed Systems and Thermal Expansion on page 14.
5. For multiple water heater installations see Water Piping

Diagrams beginning on page 67.

water piping diagrams
This manual provides detailed water piping diagrams for typical

methods of application for the water heaters, see Water Piping

Diagrams beginning 67.
The water heater may be installed by itself, or with a separate

storage tank. When used with a separate storage tank, the

circulation may be either by gravity or by means of circulating

pump. When a circulating pump is used, it is important to note

that the flow rate should be slow so that there will be a minimum

of turbulence inside the water heater storage tank.
Adjust flow by throttling a full port ball valve installed in the

circulating line on the outlet side of the pump. Never throttle flow

on the suction side of a pump. See the Water Piping Diagrams

beginning on page 67.
note: In addition to the factory installed Temperature-Pressure

Relief Valve (T&P valve) on the water heater, each remote

storage tank that may be installed and piped to a water heating

appliance must also have its own properly sized, rated and

approved Temperature-Pressure Relief Valve installed.
Call the toll free technical support phone number listed on the

back cover of this manual for further assistance in sizing a T&P

valve for remote storage tanks.
thermometers (not supplied)
Thermometers are installed in the water piping system as a

means of detecting the temperature of the hot water supply

at critical points in the system. Field supplied thermometers

should be obtained and installed. See Water Piping Diagrams

on page 67.
water (potable) heating and space heating
1. All water piping components connected to the water heater

that are for space heating applications shall be suitable for

use with potable water.

2. Toxic chemicals, such as those used for boiler treatment,

must NEVER be introduced into this system.

3. The water heaters covered in this manual may never be

connected to any existing heating system or component(s)

previously used with non-potable water heating appliance.

4. When the system requires water for space heating that

exceed safe temperatures at domestic water fixtures a

mixing valve must be installed, see Mixing Valves on page 14.