locating the water heater

Carefully choose a location for the new water heater. The

placement is a very important consideration for the safety of the

occupants in the building and for the most economical use of the

appliance.

Property Damage Hazard

All water heaters eventually leak.

Do not install without adequate drainage.

CAUTION

Whether replacing an existing water heater or installing the water

heater in a new location observe the following critical points:
1. The water heater must be located indoors.
2. The water heater must not be located in an area where it will

be subject to freezing temperatures.

3. Locate the water heater so it is protected and not subject to

physical damage by a moving vehicle.

4. Locate the water heater on a level surface.
5. Locate the water heater near a floor drain. The water heater

should be located in an area where leakage of the tank or

connections will not result in damage to the area adjacent

to the water heater or to lower floors of the structure. When

such locations cannot be avoided, it is recommended that a

metal drain pan, adequately drained, be installed under the

appliance.

6. Locate the water heater close to the point of major hot water

usage.

7. Locate the water heater close to a 120 VAC power supply.

See Power Supply on page 13 for requirements.

8. Locate the water heater where an adequate supply of fresh

air for combustion and ventilation can be obtained. See Air

Requirements on page 17.

9. Locate the water heater where the vent and intake air piping,

when installed, will remain within the maximum equivalent

lengths allowed. See Venting Requirements on page 22.

10. Do not locate the water heater where noise (such as

the Combustion Blower) during normal operation will be

objectionable in adjacent areas.

11. Do not locate the water heater where the subsequent

installation of the vent (exhaust) or intake air terminations

would be objectionable due to noise at the termination(s).

This includes locations close to or across from windows and

doors. See Venting Installation on page 21.

Fire or Explosion Hazard

Read instruction manual before

installing, using or servicing

water heater.

Avoid all ignition sources if you smell gas.

Do not store or use gasoline or other flammable vapors and

liquids in the vicinity of this or any other appliance.

Use only the gas shown on the water heater rating label.

Keep ignition sources away from faucets after extended

periods of non-use.

Maintain required clearances to combustibles.

Do not expose water heater controls to excessive gas

pressure.

There is a risk in using fuel burning appliances such as gas water

heaters in rooms, garages or other areas where gasoline, other

flammable liquids or engine driven equipment or vehicles are

stored, operated or repaired. Flammable vapors are heavy and

travel along the floor and may be ignited by the water heater’s

igniter or Main Burner flames causing fire or explosion.

Flammable items, pressurized containers or any other potential fire

hazardous articles must never be placed on or adjacent to the water

heater.

clearance to combustible materials
The water heaters covered in this manual are approved for

installation on combustible flooring. The clearance to combustible

and non combustible construction materials is 0 inches on the

back and sides of the water heater. These water heaters are also

approved for installation in an alcove.
note: Adequate clearance for servicing should be maintained

on all installations. See Service Clearance below.

TOP VIEW

0

0

0

ALCOVE

FRONT VIEW

CLEARANCES TO COMBUSTIBLE

AND NON COMBUSTIBLE

CONSTRUCTION MATERIALS

WATER

HEATER

FRONT

TOP COVER

FRONT

figure 7

serVice clearance
A service clearance of 24 inches (61 cm) should be maintained

from serviceable parts such as the T&P valve, control system

components, gas valve, clean out opening, drain valve, the vent

connection (exhaust elbow) and the condensate drain. Leave as

much room as possible above the water heater and near the

exhaust elbow for this reason. See Figure 9 on page 16.
intake air and Vent pipe clearances
The minimum clearance from combustible materials for the vent

(exhaust) and intake air piping shall be 0 inches. Vent or intake

air piping passing through a combustible wall or ceiling must be

a continuous run (no joints).