Blower prover failure, Blower prover open, Blocked air intake – American Water Heater HCG3 130T 300 User Manual

Page 59: Energy cut out (eco)

background image

59

fault and alert messages (cont)

Call the technical support phone number listed on the back cover for further technical assistance or to locate a qualified service agent

in your area.

possible causes - check/repair

displayed fault/alert message

• The control system has detected the Blower Prover Switch

contacts are closed when they should be open at the beginning of

a heating cycle - see the Sequence Of Operation on page 59.

• Pinched/shorted Blower Prover Switch wiring - see Figure 3 on

page 8 for switch location.

• Jumper wire connected to the Blower Prover Switch - remove

jumper wire. Jumper wires must never be used, read all Warnings

on page 57.

• Excessive wind outdoors pressurizing the vent system piping.
• Excessive negative air pressure in the installed space.

CHANGE

BACK

ADVANCED

Blower Prover Failure

Fault occurred 2 mins ago

The blower prover switch is

closed out of sequence.

Call a service professional:

Your Company Name Here

(press [DOWN] for more....)

• The control system has detected the Blower Prover Switch

contacts are remaining open after the control system has

energized the Combustion Blower - see the Sequence Of

Operation on page 59.

• Loose or open wiring to the Blower Prover Switch - see Figure 3 on

page 8 for switch location.

• Blower Prover Switch air sensing tube disconnected, kinked, filed

with condensate, damaged or leaking - repair or replace tube.

• Combustion Blower is not running when energized.
• Loose or open wiring to Combustion Blower.
• Loose, open, incorrect wiring to the VFD on AHCG3 130T 400

models - see Figure 3 on page 8 and the wiring diagram on page 65.

CHANGE

BACK

ADVANCED

Blower Prover Open

Fault occurred 2 mins ago

The blower prover switch remains

open after the blower has been

energized.

Call a service professional:

Your Company Name Here

(press [DOWN] for more....)

• The control system has detected the Blocked Intake Air Switch

contacts are open.

• Loose or open wiring to the Blocked Intake Air Switch - see Figure

3 on page 8 for switch location.

• Excessive equivalent pipe length, exceeded the maximum number

of 90° elbows or wrong pipe size used in the intake air piping

system - see Venting Requirements on page 22.

• Balance plate and/or intake air screen was not removed prior to

connecting the intake air piping to the water heater and is clogged/

blocked with debris - see Figure 17 on page 24.

• Excessive negative air pressure in the installed space.

CHANGE

BACK

ADVANCED

Blocked Air Intake

Fault occurred 2 mins ago

The combustion air intake is

restricted.

Call a service professional:

Your Company Name Here

(press [DOWN] for more....)

• The control system has detected the ECO (energy cut out) Switch

contacts are open.

• The ECO switch is a normally closed switch that opens on a

temperature rise to prevent excessive water temperature in the

storage tank. The ECO switch is inside the Upper Temperature

Probe (two red wires) - see Figure 3 on page 8 for Upper Probe

location.

• Loose or open wiring to the ECO switch in the Upper Temperature

Probe - two red wires.

• Improper water system piping and/or excessively high return

(recirculation) loop water temperature - see the Water Piping

Diagrams beginning on page 67.

CHANGE

BACK

ADVANCED

Energy Cut Out (ECO)

Fault occurred 2 mins ago

Tank temperature is excessive.

The water heater has been

disabled.

Call a service professional:

Your Company Name Here

(press [DOWN] for more....)

• The control system has not detected any voltage from the powered

anode rods - see Figure 3 on page 8 for location.

• No water in the storage tank.
• Loose or open wiring connections to the powered anode rods - see

Figure 3 on page 8 for location.

• Powered anode rod wiring shorted to ground.
• The water heater is not properly grounded - see Power Supply

Connections on page 39.

• Loose or open ground wires.
• Top fitting (3/4 inch bushing) of the powered anode rods were

saturated with water during installation - with power to the water

heater turned off, carefully remove anode rods and dry out

bushing(s).

CHANGE

BACK

ADVANCED

No Anode Voltage

Alert:

Alert occurred 2 mins ago

No voltage detected from

Powered Anode(s).

Call a service professional:

Your Company Name Here

(press [DOWN] for more....)