beautypg.com

Installation considerations, Rough in dimensions, Recovery capacities – American Water Heater HCG3 130T 300 User Manual

Page 10: Table 2, Gas line connection size table 1, Storage capacities table 3

background image

10

table 2

Model

U.S. Gallons

Liters

ASmE

Standard

ASmE

Standard

(A)HCG-130300

130

119.9

492

453.8

(A)HCG-130400

130

119.9

492

453.8

(A)HCG-130500

130

119.9

492

453.8

figure 6

These designs comply with the current edition of the American National Standard for Gas Water Heaters, Volume III, ANSI Z21.10.3

/ CSA 4.3 as an automatic circulating tank water heater, and automatic storage water heaters.

rough in dimensions

gas line connection siZe
table 1

Model

Series

Natural Gas

Propane Gas

(A)HCG3 130T 300

100/101

1 1/4” NPT

1 1/4” NPT

(A)HCG3 130T 400

100/101

1 1/4” NPT

1 1/4” NPT

This table shows connections sizes only - see Table 5 on page 13 for minimum

required supply gas line sizes. Depending on the installed equivalent length,

and/or the number of appliances connected, the supply gas line size may have

to be increased beyond the minimum required sizes - see Gas Line Sizing on

page 37.

storage capacities

table 3

u. s. gallons/hr & liters/hr at temperature rise indicated

Model

Type of

Gas

Input

°F

20°F

30°F

40°F

50°F

60°F

70°F

80°F

90°F

100°F 110°F 120°F 130°F 140°F

btu/hr

kW

°C

11°C

17°C

22°C

28°C

33°C

39°C

44°C

50°C

56°C

61°C

67°C

72°C

78°C

(A)HCG 130T

300

Natural

300,000

88

GPH

1746

1164

873

699

582

499

436

388

349

318

291

269

250

Propane

LPH

6610

4406

3304

2644

2203

1888

1652

1469

1322

1201

1102

1017

945

(A)HCG3 130T

400

Natural

399,900 117

GPH

2328

1552

1164

931

776

665

582

517

466

423

388

359

332

Propane

LPH

8813

5875

4406

3525

2938

2518

2203

1958

1763

1602

1469

1356

1259

Recovery capacities are based on 96% thermal efficiency.

installation considerations

35°

20°

70°

18°

45°

45°

CL

EA

NO

UT

T &

P

VA

LV

E

G

AS

*1 1/2” NPT

WATER

OUTLET

FRONT

TOP

DRAIN V

AL

VE

INTAKE AIR

4 INCH PVC

VENT

4 INCHPVC

FRONT

BACK

CLEANOUT

T & P

3/4” NPT

DRAIN

1 1/2” NPT

WATER INLET

4” PVC

VENT CONNECTION

(exhaust elbow)

4” PVC

INTAKE AIR

CONNECTION

1 1/4” SUPPLY GAS

CONNECTION

33.12” (84.1 cm)

OUTSIDE

DIAMETER

4.86”

(12.34 cm)

50.77”

(129 cm)

75.50”

(191.8 cm)

69”

(175.3 cm)

69”

(175.3 cm)

12”

(30.5 cm)

* Center line of water outlet on top of the water heater is 7 inches from the front edge of the water heater.

WATER

OUTLET

HEIGHT

63 INCHES

(160 cm)

CONDENSATE

DRAIN CONNECTION

1/2 INCH PVC

recoVery capacities