beautypg.com

System specifications, 0 system specifications – APC 60-80kW User Manual

Page 76

background image

76

Installation Guide APC Silcon 60-80kW 400V UPS

990-4051

System Specifications

7.0 System Specifications

7.1

Technical Data

7.2

Dimensions / Weight

Voltage

3x380/400/415V

Input

Voltage tolerance
Normal operation
Bypass operation

+15%
+10% (standard)
+4, 6, 8% (programmable)

Frequency

50Hz/60Hz
+6 standard
+0.5-8% (programmable)

Input power factor

load 25% minimum 0.97
load 100% minimum 0.99

Current distortion

Max. 5%

Output

Voltage

3x380/400/415V

Voltage tolerance

+1% static symmetrical load
+3% static symmetrical load
+5% 0-100% load step

Voltage distortion

max. 3% linear load
max. 6% non-linear load

Load power factor

0.9 lead to 0.8 lag

Frequency

50Hz/60Hz (mains synchronized)
+0.1% free-running

Overload capacity
Mains operation
Mains operation
Battery operation
Bypass operation

200% - 60 seconds
125% - 10 minutes
150% - 30 seconds
125% - continuous

General

Ambient temperature

0-40

o

C (Temperatures above 25

o

C will

reduce battery lifetime)

Humidity
Protection class
Safety

Emission and Immunity
Static bypass switch
Auto restart
Economy mode

Max. 95% non-condensing
IP30
EN 50091-1
CE Mark
EN 50091-2
Built-in
Programmable
Programmable

Type

60kW

80kW

Height [mm]

1400

1400

Width [mm]

800

800

Depth [mm]

800

800

Weight [kg]

410

440