System specifications, 0 system specifications – APC 60-80kW User Manual
Page 76
76
Installation Guide APC Silcon 60-80kW 400V UPS
990-4051
System Specifications
7.0 System Specifications
7.1
Technical Data
7.2
Dimensions / Weight
Voltage
3x380/400/415V
Input
Voltage tolerance
Normal operation
Bypass operation
+15%
+10% (standard)
+4, 6, 8% (programmable)
Frequency
50Hz/60Hz
+6 standard
+0.5-8% (programmable)
Input power factor
load 25% minimum 0.97
load 100% minimum 0.99
Current distortion
Max. 5%
Output
Voltage
3x380/400/415V
Voltage tolerance
+1% static symmetrical load
+3% static symmetrical load
+5% 0-100% load step
Voltage distortion
max. 3% linear load
max. 6% non-linear load
Load power factor
0.9 lead to 0.8 lag
Frequency
50Hz/60Hz (mains synchronized)
+0.1% free-running
Overload capacity
Mains operation
Mains operation
Battery operation
Bypass operation
200% - 60 seconds
125% - 10 minutes
150% - 30 seconds
125% - continuous
General
Ambient temperature
0-40
o
C (Temperatures above 25
o
C will
reduce battery lifetime)
Humidity
Protection class
Safety
Emission and Immunity
Static bypass switch
Auto restart
Economy mode
Max. 95% non-condensing
IP30
EN 50091-1
CE Mark
EN 50091-2
Built-in
Programmable
Programmable
Type
60kW
80kW
Height [mm]
1400
1400
Width [mm]
800
800
Depth [mm]
800
800
Weight [kg]
410
440