Installation Guide APC Silcon 60-80kW 400V UPS

990-4051

Options/Accessories

6.6

Remote Display

With the remote display unit data may be displayed at distances of up to 25 m from UPS. For
extended communication distance, see section below.

Remote display may easily be connected to UPS via one of the two serial communication ports
on the communication interface board.

To obtain a transmission distance of up to 3.2 km normal RS232C signal levels must be
converted to a long distance communication standard. The converter must be placed outside
the UPS cabinet.

6.6.1 Extension of Remote Display Communication Distance

Remote display communicates with the UPS through a 3-wire RS232 interface. Remote display
is a DTE (Data Terminal Equipment) employing a SUB-D 9-pin female connector.
Communication speed: 9600 bps.

For communication distances, see Table 1. Insert converters if longer distances are necessary,
or if communication cables are led through magnetically noisy areas. Converters must comply
with local regulations

Table 1: Remote Display Communication Extensions

Two converter boxes are required for a communication distance extension: One
box near the UPS for the conversion from RS232C to a long distance communication standard,
and another box at the other end to convert back to RS232C, which is to be connected to the
Remote Display. The converter provides optical signal insulation. Both converter boxes must
be supplied by an uninterruptible power source.

Standard
(RS232)

Short-haul
Modem Async

Max. distance

80/25 ft/m

10000/3200 ft/m

Converter Manufacture
Art. Code

No converter

BLACK BOX
ME800A-R2

RS232 BLACK BOX connector

Sub-D 25-pin female

BLACK BOX interconnector

4-screw terminal