Programming parameters – APC 60-80kW User Manual

Page 39

background image

Programming Parameters

990-4051

Installation Guide APC Silcon 60-80kW 400V UPS

39

System Configuration Parameters (password protected)

* Bold text refers to factory standard setting
**Advanced Battery Monitor

Parameter

Setting*

Comments

Isolation Transformer Input

YES, NO

YES if optional input isolation transformer is available

IsolationTransformer
Output

YES, NO

YES if optional output isolation transformer is available

Delta Soft Start Time

1, 10, 20, 40 sec.

Input current switching in ramp function. Use higher
values for smaller/unstable diesel generators

External SSW present

YES, NO

YES for systems with external static bypass switch

Normal Charge Voltage

410-460V
438V

Setting of float charge voltage at 20°C
(Automatic compensation for temperature deviations)

Boost Charge Voltage

438-460V
438V

Setting of boost charge voltage at 20°C
(Automatic compensation for temperature deviations)

Low Battery warning

336-384V
336V

Discharged Battery warning

Low Battery shut-down

310-336V
326V

Switches off system at min. permissible battery
voltage

Synchronization

0.25, 0.5, 1, 2, 4
Hz/sec.

Syncronization speed.

High Battery Temperature

15-40°C
35°C

Alarm - Ambient temperature for battery too high

Common fault delay

0, 10, 20,
30 sec.

Delay before common fault alarm relay is activated

Reset operation mode lock

YES, NO

YES resets system locked in bypass or battery
operation mode caused by system failures (only
applicable for service personnel)

Expected back-up time
(min.)

0.1-999.9
5.0

Expected UPS back-up time in minutes when running
at 100% ohmic load. Time used by ABM**

Battery Capacity in (Ah)

0.1-999.9
7.0

Total Battery capacity in Ah.
Setting used by ABM**.

Highest Station Address

2-9

Highest station address in parallel system

Station Address

1-9

Station address in parallel system

APM Mode Active
(Advanced Power
Management)

Disabled
Redundant +1
Parallel +1

Use only in parallel systems.
Disabled: Advanced power management off.
Redundant +1: Redundant operation with one unit
being inactive in parallel system
Parallel +1: Redundant operation with all units in
operation.

APM Test Mode Active

YES, NO

YES, if APM test mode is active

Battery Connection

Common,
Separate

Common: if common battery is used in parallel system.
Separate: if separate battery is used