beautypg.com

Sterlco GC Series Central Chiller User Manual

Page 51

background image

GC Series Central Chillers

Chapter 6: Troubleshooting

51 of 79

Code

VFD Alarm

Possible Cause

Solution

line phase or blown fuse. Fault trip
occurs when DC voltage ripple
exceeds 14% of nominal DC voltage.

Check for input power supply
imbalance.

Check fault function parameter
setting.

F0034

MOTOR PHASE

Motor circuit fault due to missing
motor phase.

Check motor and motor cable.