Chapter 6: Troubleshooting
50 of 79
Controller Alarm
Possible Cause
Solution
Faulty sensor cable
Replace cable
Faulty sensor
Replace sensor
Low Suction Pressure at Startup
Contact ACS Group Aftermarket
Service for assistance
Troubleshooting the ABB Variable Speed Drive
If a current alarm exists, the drive will be flashing a fault code on the LED display. Below is a table of
common faults and their corrections.
NOTE: If a fault code is not listed in the table below contact ACS Group Aftermarket Service at [800]
423-3183.
Code
VFD Alarm
Possible Cause
Solution
F0001
OVERCURRENT
Output current has exceeded trip level.
Overcurrent trip limit for drive is
325% of drive nominal current.
Check motor load.
Check motor and motor cable
(including phasing).
Check ambient conditions. Load
capacity decreases if installation site
ambient temperature exceeds 40°C.
F0002
DC OVERVOLT
Excessive intermediate circuit DC
voltage. DC overvoltage trip limit is
420 V for 200 V drives and 840 V for
400 V drives.
Check that overvoltage controller is on
(parameter 2005 OVERVOLT CTRL).
Check input power line for static or
transient overvoltage.
Call ACS Group Aftermarket Service
F0003
DEV OVERTEMP
Drive IGBT temperature is excessive.
Fault trip limit is 135°C.
Check ambient conditions.
Check air flow and fan operation.
Check motor power against unit
power.
F0004
SHORT CIRC
Short circuit in motor cable(s) or
motor
Check motor and motor cable.
F0006
DC UNDERVOLT
Intermediate circuit DC voltage is not
sufficient due to missing input power
line phase, blown fuse, rectifier bridge
internal fault or too low input power.
DC undervoltage trip limit is 162 V
for 200 V drives and 308 V for 400
Drives
Check that undervoltage controller is
on (parameter 2006 UNDERVOLT
CTRL).
Check input power supply and fuses.
F0016
EARTH FAULT
Drive has detected earth (ground) fault
in motor or motor cable.
Check motor.
Check fault function parameter
setting.
Check motor cable. Motor cable
length must not exceed 50’.
F0018
THERM FAIL
Drive internal fault. Thermistor used
for drive internal temperature
measurement is open or short-
circuited.
Check the cooling fan for failure.
Contact ACS Group Aftermarket
Service
F0022
INPUT PHASELOSS Intermediate circuit DC voltage is
oscillating due to missing input power
Check input power line fuses.