Chapter 6: Troubleshooting
47 of 79
Problem
Possible cause
Solution
Compressor not operating
efficiently.
Call service.
Unit under-sized for application.
Call sales rep
Troubleshooting Warnings and Faults from the PLC
Controller Alarm
Possible Cause
Solution
Compressor Fault
Compressor Internal Overload Fault Allow time to cool and reset, then
check for high/low voltage. It must be
within ±10% of the nameplate rating.
Compressor Motor Circuit
Protector Open
Verify switch is in the “ON” position
Verify amp value is at its highest
Check for high/low line voltage. It
must be within ±10% of the nameplate
rating
Discharge Pressure Sensor Failure
Packard connector separated from
sensor
Reconnect wire connector to sensor
Input to PLC is missing
Verify wiring at PLC.
Faulty sensor cable
Replace cable
Faulty sensor
Replace sensor
VFD Fault
See Troubleshooting the ABB
Variable Speed Drive below
See Troubleshooting the ABB Variable
Speed Drive below
Fan VFD fuses blown
Replace fuses
Fan motor overload tripped
Reset overload/verify overload setting
Input to PLC is missing
Verify wiring at digital input ID4 at
PLC
High Discharge Pressure Fault
(Discharge pressure has exceeded
fault setpoint)
See VFD Fault above
See VFD Fault above
Condenser inlet temperature too
high
Contact ACS Group Aftermarket
Service for assistance
Refrigerant overcharge
Contact refrigeration technician about
removing refrigerant as needed
Dirty condenser
Clean condenser
Fan motor failure
Verify fan motor operation, replace as
needed
No analog output from PLC
Verify wiring at analog output J4 per
print.
Verify VFD AI Type selector switch is
in the U position.
High Discharge Pressure Switch
(Discharge pressure has exceeded
switch 575 psig setting)
Input to PLC is missing
Verify wiring at digital input ID2 at
PLC
VFD Fault
See VFD Fault above
Condenser inlet temperature too
high
Contact ACS Group Aftermarket
Service for assistance
Refrigerant overcharge
Contact refrigeration technician about
removing refrigerant as needed
Dirty condenser
Clean condenser
Fan motor failure
Verify fan motor operation, replace as
needed
No analog output from PLC
Verify wiring at analog output J4 per
print.
Verify VFD AI Type selector switch is
in the U position.
High Suction Pressure Fault
(Suction pressure has exceeded
fault setpoint)
Load may be too high for chiller
Contact your sales representative for
assistance.
Low Discharge Pressure Fault
(Discharge pressure has fallen
below fault setpoint)
Condenser inlet temperature too
low
Contact ACS Group Aftermarket
Service for assistance
VFD fault
See VFD Fault above
Condenser water regulating valve
open
Verify analog output at Y1