Chapter 6: Troubleshooting
48 of 79
Controller Alarm
Possible Cause
Solution
Low Fluid Temp Fault (Leaving
fluid temperature has dropped
below the fault setpoint)
Optional Hot gas bypass valve
malfunction
Verify wiring EV Connection B1-4 on
EVD
Low Suction Pressure Fault
(Suction pressure has fallen below
fault setpoint)
Refrigerant undercharge
Contact refrigeration technician about
adding refrigerant as needed
Refrigerant leak
Contact refrigeration technician about
repairing lead and adding refrigerant as
needed
Electronic expansion valve closed
Verify wiring EV Connection A1-4 on
EVD
Low fluid flow through evaporator
Verify evaporator inlet and outlet
butterfly valve position to achieve 10°F
(5.6°C) differential across evaporator
Clean evaporator inlet strainer
Verify evaporator pump operation
Leaving fluid temperature close to
Fluid Freezepoint Setpoint
Verify Fluid Freezepoint setpoint and
glycol/water mixture for proper
freezing temperature
Low Superheat Fault (Superheat
calculated value has dropped
below fault setpoint)
Electronic expansion valve
malfunction
Verify wiring at EV Connection A1-4
Contact refrigeration technician about
replacing valve as needed
Suction Pressure Sensor Failure
Packard connector separated from
sensor
Reconnect wire connector to sensor
Input to PLC is missing
Verify wiring at EVD
Faulty sensor cable
Replace cable
Faulty sensor
Replace sensor
Leaving Water Temp Sensor
Failure
Input to PLC is missing
Verify wiring at PLC
Faulty sensor
Replace sensor
Low Level Fault (optional: will
only become active if level sensor
is enabled in Supervisor Menu)
Fluid level too low in tank
Add fluid to pump tank to a minimum
of 18 in (46 cm) above the pump
suction centerline while the pump is
operating
Sensor failure
See Level Sensor Fault
No Flow
Circulation pump is faulty
Verify operation of circulation pump
Input to PLC is missing
Verify wiring at ID3 on PLC
M12 connector on cable separated
from sensor
Reconnect M12 connector to top of
sensor.
Faulty sensor cable
Replace cable
Faulty sensor
Replace sensor
High Fluid Temp Fault (Leaving
fluid temperature has exceeded
fault setpoint)
Compressor fault
See Compressor Fault above
Load may be too high for chiller
Contact your sales representative for
assistance.
Evaporator dirty
Clean evaporator inlet strainer
Back flush evaporator
Condenser Differential Pressure
Warning
Condenser dirty
Clean condenser
Condenser Inlet Temp Sensor
Failure
Input to PLC is missing
Verify wiring at PLC
Faulty sensor
Replace sensor
Chiller In Fluid Temp Sensor
Failure
Input to PLC is missing
Verify wiring at PLC
Faulty sensor
Replace sensor
Evaporator Differential Pressure
Dirty evaporator
Clean evaporator inlet strainer
Back flush evaporator
High Discharge Pressure Warning
Dirty condenser
Clean condenser
High Fluid Temp Warning
Leaving fluid temperature has
exceeded warning setpoint
High Level Fault (optional: will
only become active if level sensor
is enabled in Supervisor Menu)
Fluid level in pump tank is above
fault setpoint
Remove fluid from pump tank to
achieve a minimum of 18 in (46 cm)
above the pump suction centerline
while the pump is operating