Pump Tanks

Chapter 4: Operation

46 of 67

Process Pump Motor Fault Alarm

While this alarm is active, the process pump is not allowed to run. If another process pump is
enabled or the stand-by pump is enabled and configured as a process, it will start after a 2
second delay.

This alarm occurs when all of the following conditions are met for 3 seconds:

• The system is online.
• The process pump is enabled.
• The process pump run input is not active.


This alarm will remain active until any of the following conditions are met:

• The system is no longer online.
• The alarm is reset.

Process VFD Fault Alarm

While this alarm is active, the process pump is not allowed to run. If another process pump is
enabled or the stand-by pump is enabled and configured as a process, it will start after a 2
second delay.

This alarm occurs when all of the following conditions are met for 3 seconds:

• The system is online.
• The process pump is enabled.
• The process VFD input is not active.


This alarm will remain active until any of the following conditions are met:

• The system is no longer online.
• The alarm is reset.

Recirc. Amp Sensor Failure

This alarm occurs when all of the following conditions are met:

• The system is online.
• The control detects a recirc amp sensor failure.


This alarm will remain active until any of the following conditions are met:

• The system is no longer online.
• The control no longer detects a recirc amp sensor failure when the alarm is reset.

Recirc. Low Flow Switch Alarm

This alarm occurs when all of the following conditions are met for the Low Flow Delay:

• The system is online.
• At least one recirc pump is active.
• The Recirc Low Flow Switch Input is not active.

The alarm will remain active until the system is taken offline or the alarm is reset.