Process Pump Motor Fault Alarm
While this alarm is active, the process pump is not allowed to run. If another process pump is
enabled or the stand-by pump is enabled and configured as a process, it will start after a 2
second delay.
This alarm occurs when all of the following conditions are met for 3 seconds:
• The system is online.
• The process pump is enabled.
• The process pump run input is not active.
This alarm will remain active until any of the following conditions are met:
• The system is no longer online.
• The alarm is reset.
Process VFD Fault Alarm
While this alarm is active, the process pump is not allowed to run. If another process pump is
enabled or the stand-by pump is enabled and configured as a process, it will start after a 2
second delay.
This alarm occurs when all of the following conditions are met for 3 seconds:
• The system is online.
• The process pump is enabled.
• The process VFD input is not active.
This alarm will remain active until any of the following conditions are met:
• The system is no longer online.
• The alarm is reset.
Recirc. Amp Sensor Failure
This alarm occurs when all of the following conditions are met:
• The system is online.
• The control detects a recirc amp sensor failure.
This alarm will remain active until any of the following conditions are met:
• The system is no longer online.
• The control no longer detects a recirc amp sensor failure when the alarm is reset.
Recirc. Low Flow Switch Alarm
This alarm occurs when all of the following conditions are met for the Low Flow Delay:
• The system is online.
• At least one recirc pump is active.
• The Recirc Low Flow Switch Input is not active.
The alarm will remain active until the system is taken offline or the alarm is reset.