Sterlco 140 to 6,285 Gallon Pump Tanks User Manual
Page 40

Pump Tanks
Chapter 4: Operation
40 of 67
High Process Pressure Fault
This alarm occurs when all of the following conditions are met:
• A process pump has been active for 15 seconds.
• The process pump pressure is greater than or equal to the High Pressure Fault
setpoint.
• The Process Pressure Sensor Failure alarm is not active.
This alarm will remain active until any of the following conditions are met:
• The system is no longer online.
• The process pump pressure is less than the High Process Pressure Fault setpoint when
the alarm is reset.
• The Process Pressure Sensor Failure alarm becomes active.
High Process Pressure Warning
This alarm occurs when all of the following conditions are met:
• A process pump has been active for 15 seconds.
• The process pump pressure is greater than or equal to the High Pressure Warning
setpoint.
• The High Process Pressure Fault is not active.
• The Process Pressure Sensor Failure alarm is not active.
This alarm will remain active until any of the following conditions are met:
• The system is no longer online.
• The process pump pressure is less than the High Process Pressure Warning setpoint
when the alarm is reset.
• The High Process Pressure Fault alarm becomes active.
• The Process Pressure Sensor Failure alarm becomes active.
High Recirc Pressure Fault
This alarm occurs when all of the following conditions are met:
• A recirc pump has been active for 15 seconds.
• The recirc pump pressure is greater than or equal to the High Recirc Fault setpoint.
• The Recirc Pressure Sensor Failure alarm is not active.
This alarm will remain active until any of the following conditions are met:
• The system is no longer online.
• The recirc pump pressure is less than the High Recirc Pressure Fault setpoint when
the alarm is reset.
• The Recirc Pressure Sensor Failure alarm becomes active.