4-6 Options – Analog Outputs

Cold Side Retransmission

The selected analog output will retransmit the Cold Side Temperature. The range of
temperature transmitted is dictated by the Cold Side Retransmission Min and Max settings.

Hot Side Retransmission

The selected analog output will retransmit the Hot Side Temperature. The range of the
temperature transmitted is dictated by the Hot Side Retransmission Min and Max.

Process 3 Way Valve

This valve is used with the Wintercooler output option. It is used to divert water around the
wintercooler to prevent over cooling.


4-7 Options – Digital Inputs

Digital inputs that are not required for the pumps and fan are configurable. The
available options can be assigned to only one input.

Alarm Silence

Allows for a push button to be installed to silence alarms.

Chiller Enable

This option allows the recirc pumps to be controlled by an outside source. When an input is
configured for Chiller Enable, the recirc pumps will not be allowed to run unless this input is
on.

Dirty Filter

Adds a Dirty Filter Alarm Input. See Alarms section of this document for more information.

Miscellaneous Alarm

Adds a Miscellaneous Alarm Input. The alarm can be configure to activate when the input is
on or off. See Alarms section of the document for more information.

Process Low Flow Switch

Adds a Process Low Flow Switch Alarm input. See Alarm section of this document for more
information

Process Low Pressure Switch

Adds a Process Low Pressure Switch Alarm input. See Alarm section of this document for
more information.