Low Recirc Pressure Warning

This alarm occurs when all of the following conditions are met:

• A recirc pump has been active for 15 seconds.
• The recirc pump pressure is less than or equal to the Low Recirc Pressure Warning

setpoint.

• The Recirc Low Pressure Fault is not active.
• The Recirc Pressure Sensor Failure alarm is not active.


This alarm will remain active until any of the following conditions are met:

• The system is no longer online.
• The recirc pump pressure is greater than the Low Recirc Pressure Warning setpoint

when the alarm is reset.

• The Recirc Low Pressure Fault alarm becomes active.
• The Recirc Pressure Sensor Failure alarm becomes active.

Low Temperature Fault

This alarm occurs when all of the following conditions are met:

• The system is online.
• The cold side temperature is less than or equal to the Low Temp Fault setpoint.
• The Cold Side Temperature Sensor Failure is not active.


This alarm will remain active until any of the following conditions are met:

• The system is no longer online.
• The tank temperature is greater than the Low Temp Fault setpoint when the alarm is

reset.

• The Cold Side Temperature Sensor Failure becomes active.

Low Temperature Warning

This alarm occurs when all of the following conditions are met:

• The system is online.
• The tank temperature is less than or equal to the Low Temp Warning setpoint.
• The Low Temperature Fault is not active.
• The Cold Side Temperature Sensor Failure is not active.


This alarm will remain active until any of the following conditions are met:

• The system is no longer online.
• The Low Temperature Fault becomes active.
• The tank temperature is greater than the Low Temp Warning setpoint when the alarm

is reset.

The Cold Side Temperature Sensor Failure becomes active.