Chapter 4: Operation
39 of 67
Evap. Inlet Temperature Sensor Failure
This alarm occurs when all of the following conditions are met:
• The system is online.
• The control detects an evap inlet temperature sensor failure.
This alarm will remain active until any of the following conditions are met:
• The system is no longer online.
• The control no longer detects an evap inlet temperature sensor failure when the alarm
is reset.
Evap. Outlet Temperature Sensor Failure
This alarm occurs when all of the following conditions are met:
• The system is online.
• The control detects an evap outlet temperature sensor failure.
This alarm will remain active until any of the following conditions are met:
• The system is no longer online.
• The control no longer detects an evap. outlet temperature sensor failure when the
alarm is reset.
High Level Fault
This alarm occurs when all of the following conditions are met:
• The system is online.
• The tank level is greater than or equal to the High Level Fault setpoint.
• The Tank Level Sensor Failure alarm is not active.
This alarm will remain active until any of the following conditions are met:
• The system is no longer online.
• The tank level is less than the High Level Fault setpoint when the alarm is reset.
• The Tank Level Sensor Failure alarm becomes active.
High Level Warning
This alarm occurs when all of the following conditions are met:
The system is online.
• The tank level is greater than or equal to the High Level Warning setpoint.
• The Tank High Level Fault is not active.
• The Tank Level Sensor Failure alarm is not active.
This alarm will remain active until any of the following conditions are met:
• The system is no longer online.
• The tank level is less than the High Level Warning setpoint when the alarm is reset.
• The Tank High Level Fault becomes active.
• The Tank Level Sensor Failure alarm becomes active