Chapter 4: Operation

43 of 67

Low Process Pressure Fault

This alarm occurs when all of the following conditions are met:

• A process pump has been active for 15 seconds.
• The process pump pressure is less than or equal to the Low Process Pressure Fault

setpoint.

• The Process Pressure Sensor Failure alarm is not active.


This alarm will remain active until any of the following conditions are met:

• The system is no longer online.
• The process pump pressure is greater than the Low Process Pressure Fault setpoint

when the alarm is reset.

• The Process Pressure Sensor Failure alarm becomes active.

Low Process Pressure Warning

This alarm occurs when all of the following conditions are met:

• A process pump has been active for 15 seconds.
• The process pump pressure is less than or equal to the Low Process Pressure Warning

setpoint.

• The Process Low Pressure Fault is not active.
• The Process Pressure Sensor Failure alarm is not active.


This alarm will remain active until any of the following conditions are met:

• The system is no longer online.
• The process pump pressure is greater than the Low Process Pressure Warning

setpoint when the alarm is reset.

• The Process Low Pressure Fault alarm becomes active.
• The Process Pressure Sensor Failure alarm becomes active.

Low Recirc Pressure Fault

This alarm occurs when all of the following conditions are met:

• A recirc pump has been active for 15 seconds.
• The recirc pump pressure is less than or equal to the Low Recirc Pressure Fault

setpoint.

• The Recirc Pressure Sensor Failure alarm is not active.


This alarm will remain active until any of the following conditions are met:

• The system is no longer online.
• The recirc pump pressure is greater than the Low Recirc Pressure Fault setpoint when

the alarm is reset.

• The Recirc Pressure Sensor Failure alarm becomes active.