SBFC Series Blown Film Cooling Systems
Page 27
5 Maintenance
5-1 Lubricating the Optional Blower
Blower and blower motor bearings require lubrication every
30 days. Use an NLGI Grade No. 2 grease, such as Chevron
Oil Co. grade SRI-2, or an equivalent.
5-2 Servicing
the
Filter
Cooling coils are equipped with a permanent filter. Make sure
that you check the filter periodically and clean it or replace it
as needed. To clean the filter, soak it in a detergent solution,
rinse in clean, cool water, and carefully shake it dry.
!
CAUTION
Do not blow off the filter with compressed air,
as you could damage the filter element.
Never run the cooler without the filter installed!
5-3 Servicing the 3-Way Valve
Adjusting the 3-Way Valve
!
CAUTION
Before disassembly, make sure that the bulb has cooled to 25ºF (-4ºC)
or below. Use ice and salt to achieve this temperature.
Also make sure that flow through the valve and lines
has stopped before disassembly.