Sterlco Micro Series Water Temperature Control Unit User Manual
Page 38

3200
Series
38 ACS 3216 Operators Manual
Input current
0 to 50mA rms calibrated, 50/60Hz
Scale
0 to 10, 25, 50 or 100Amps
Input
impedance
<20
Ω
Accuracy
+4% of reading
Alarms
Leakage current, overcurrent
Indication
Custom scrolling message and beacon
Types
High, low, deviation band, sensor fault, load leakage current, over current,
internal events
Recipes
Number
5
Parameters
stored
38
Selection
Key press or via remote communications
General
Text Messages
10 x 30 character messages
Dimensions and weight
48W x 48H x 90Dmm (1.89W x 1.89H x 3.54D in) 8.82oz (250g)
Power Supply
100 to 240Vac -15%, +10%. 48 to 62Hz. 5 watts max
Temperature and RH
Operating: 32 to 131°F (0 to 55°C), RH: 5 to 90% non-condensing.
Storage temperature
-10 to 70°C (14 to 158°F)
Panel sealing
IP 65, plug-in from front panel
Safety standards
EN61010, installation category II (voltage transients must not exceed
2.5kV), pollution degree 2.
Electromagnetic compatibility
EN61326-1 Suitable for domestic, commercial and light industrial as
well as heavy industrial environments. (Class B emissions, Industrial
Environment immunity).
Low supply voltage versions are suitable for industrial environments
only.
Atmospheres
Not suitable for use above 2000m or in explosive or corrosive
atmospheres.