3200 Series

ACS 3216 Operators Manual 15

and vice versa

OP

Output power demand re-transmission

none

No event connected to the output

2.SRC.A

I/O 2 SOURCE
A

AL1

Alarm 1 *

AL2

Alarm 2 *

2.SRC.B

I/O 2 SOURCE
B

AL3

Alarm 3 *

AL4

Alarm4 *

2.SRC.C

I/O 2 SOURCE
C

ALL.A

All alarms

nw.AL

Any new alarm

Ct.AL

CT alarm, load, leak & overcurrent

Lbr

Loop break alarm

Sbr

Sensor break alarm

t.End

Timer end status

t.run

Timer run status

mAn

Manual status

rmt.F

Remote fail

Pwr.f

Power fail

2.SRC.D

I/O 2 SOURCE
D

These parameters only appear
when the channel function is a
Digital OP,

i.e. 2.FUNC =

d.Out

Selects an event status to be
connected to the output
channel.

The output status is the result
of an OR of Src A, Src B, Src
C, and Src D

Up to four events can,
therefore, operate the output

prg.e

Programmer event.

none

Conf

2.PLS

OUTPUT
MINIMUM
PULSE TIME

Minimum output on/off time.

Only applies to time
proportioning outputs and
prevents relays from switching
too rapidly

0.0 to

150.0

Auto or 1.0 to 150.0 seconds
Auto = 110mS

5.0 sec for
relay

Auto for
logic

Conf

nor

Normal

2.SENS

SENSE

To configure the polarity of
output channel 2

Inv

Inverted

nor

Conf

0.20

0-20mA output

2 . r n g

DC OUTPUT
RANGE

To configure 0-20mA or 4-
20mA output

Only appears if the output
module is DC output

4.20

4-20mA output

L3

AA RELAY ‘aa’

Name

Scrolling

Display

Parameter Description

Value

Default

Access Level

4.TYPE

OUTPUT 4
TYPE

Output channel 4 hardware
type

reLy

Relay output

reLy

Read only

none

Disabled

d.OUt

Conf

d.OUt

Digital output

UP

Valve open codes VC and VP only

dwn

Valve close codes VC and VP only

Heat

Heat output

4.FUNC

FUNCTION

Output channel 4 function

If the instrument is ordered as
valve positioner (codes VC or
VP), only options available are
,

none, d.out, UP, or

dwn

Note: If output 4 is set to

up

ensure the other valve
position output is set to

dwn

and vice versa

CooL

Cool output

none

No event connected to the output

4.SRC.A

I/O 4 SOURCE
A

AL1

Alarm 1 *

AL2

Alarm 2 *

4.SRC.B

I/O 4 SOURCE
B

AL3

Alarm 3 *

AL4

Alarm4 *

4.SRC.C

I/O 4 SOURCE
C

ALL.A

All alarms

nw.AL

Any new alarm

Ct.AL

CT alarm, load, leak & overcurrent

Lbr

Loop break alarm

Sbr

Sensor break alarm

t.End

Timer end status

t.run

Timer run status

mAn

Manual status

rmt.F

Remote fail

Pwr.f

Power fail

4.SRC.D

I/O 4 SOURCE
D

These parameters only appear
when the channel function is a
Digital OP,

i.e. 4.FUNC =

d.Out

Selects an event status to be
connected to the output
channel.

The output status is the result
of an OR of Src A, Src B, Src
C, and Src D

Up to four events can,
therefore, operate the output

prg.e

Programmer event.

none

Conf

4.PLS

OUTPUT
MINIMUM
PULSE TIME

Minimum output on/off time.

Only applies to time
proportioning outputs and
prevents relays from switching
too rapidly

0.0 to

150.0

0 to 150 seconds

5.0 sec

Conf