Sterlco Micro Series Water Temperature Control Unit User Manual
Page 15
3200 Series
ACS 3216 Operators Manual 15
and vice versa
OP
Output power demand re-transmission
none
No event connected to the output
2.SRC.A
I/O 2 SOURCE
A
AL1
Alarm 1 *
AL2
Alarm 2 *
2.SRC.B
I/O 2 SOURCE
B
AL3
Alarm 3 *
AL4
Alarm4 *
2.SRC.C
I/O 2 SOURCE
C
ALL.A
All alarms
nw.AL
Any new alarm
Ct.AL
CT alarm, load, leak & overcurrent
Lbr
Loop break alarm
Sbr
Sensor break alarm
t.End
Timer end status
t.run
Timer run status
mAn
Manual status
rmt.F
Remote fail
Pwr.f
Power fail
2.SRC.D
I/O 2 SOURCE
D
These parameters only appear
when the channel function is a
Digital OP,
i.e. 2.FUNC =
d.Out
Selects an event status to be
connected to the output
channel.
The output status is the result
of an OR of Src A, Src B, Src
C, and Src D
Up to four events can,
therefore, operate the output
prg.e
Programmer event.
none
Conf
2.PLS
OUTPUT
MINIMUM
PULSE TIME
Minimum output on/off time.
Only applies to time
proportioning outputs and
prevents relays from switching
too rapidly
0.0 to
150.0
Auto or 1.0 to 150.0 seconds
Auto = 110mS
5.0 sec for
relay
Auto for
logic
Conf
nor
Normal
2.SENS
SENSE
To configure the polarity of
output channel 2
Inv
Inverted
nor
Conf
0.20
0-20mA output
2 . r n g
DC OUTPUT
RANGE
To configure 0-20mA or 4-
20mA output
Only appears if the output
module is DC output
4.20
4-20mA output
L3
AA RELAY ‘aa’
Name
Scrolling
Display
Parameter Description
Value
Default
Access Level
4.TYPE
OUTPUT 4
TYPE
Output channel 4 hardware
type
reLy
Relay output
reLy
Read only
none
Disabled
d.OUt
Conf
d.OUt
Digital output
UP
Valve open codes VC and VP only
dwn
Valve close codes VC and VP only
Heat
Heat output
4.FUNC
FUNCTION
Output channel 4 function
If the instrument is ordered as
valve positioner (codes VC or
VP), only options available are
,
none, d.out, UP, or
dwn
Note: If output 4 is set to
up
ensure the other valve
position output is set to
dwn
and vice versa
CooL
Cool output
none
No event connected to the output
4.SRC.A
I/O 4 SOURCE
A
AL1
Alarm 1 *
AL2
Alarm 2 *
4.SRC.B
I/O 4 SOURCE
B
AL3
Alarm 3 *
AL4
Alarm4 *
4.SRC.C
I/O 4 SOURCE
C
ALL.A
All alarms
nw.AL
Any new alarm
Ct.AL
CT alarm, load, leak & overcurrent
Lbr
Loop break alarm
Sbr
Sensor break alarm
t.End
Timer end status
t.run
Timer run status
mAn
Manual status
rmt.F
Remote fail
Pwr.f
Power fail
4.SRC.D
I/O 4 SOURCE
D
These parameters only appear
when the channel function is a
Digital OP,
i.e. 4.FUNC =
d.Out
Selects an event status to be
connected to the output
channel.
The output status is the result
of an OR of Src A, Src B, Src
C, and Src D
Up to four events can,
therefore, operate the output
prg.e
Programmer event.
none
Conf
4.PLS
OUTPUT
MINIMUM
PULSE TIME
Minimum output on/off time.
Only applies to time
proportioning outputs and
prevents relays from switching
too rapidly
0.0 to
150.0
0 to 150 seconds
5.0 sec
Conf