Sterlco Micro Series Water Temperature Control Unit User Manual
Page 18

3200
Series
18 ACS 3216 Operators Manual
S A F E
SAFE OUTPUT POWER
To set the output level in a sensor break (open 
circuit) condition 
-100.0 to 100.0% limited by OP.HI and OP.LO
0.0%
L3
none
Transfer between Auto/Manual/Auto is 
bumpless 
SteP
Transfer from Auto to Manual, the output 
goes to a pre-set value (F.OP) 
F . M O D
FORCED MANUAL OUTPUT MODE
Selects how the loop behaves on transfer from 
Auto to Manual. 
Transfer from Manual to Auto is always 
bumpless. 
Last
Transfer from Auto to Manual, the output 
goes to the previously set manual value 
none
L3
Lin
Linear
OIL
Oil cooling
H20
Water cooling
C o o l . t
NON-LINEAR COOLING TYPE
This selects an algorithm most suited to the 
type of cooling. Typically used in extruders. 
Fan
Forced air cooling
As order 
code 
Conf
F . O P
FORCED OUTPUT
To pre-set a value for the Manual output 
when F.MOD = STEP 
-100.0 to 100.0% limited by OP.HI and OP.LO
0.0
L3
Auto
To select automatic operation
Man
To select manual operation
A - M
LOOP MODE – AUTO MANUAL OFF
OFF
Control outputs inhibited
L3
No
l b r
LOOP BREAK STATUS
YES
Shows the current status of loop break.
Read only
ALARM LIST
‘ALARM’
Name
Scrolling Display
Parameter Description
Value
Default
Access 
Level 
none
Alarm not configured
Hi
Full Scale High
Lo
Full Scale Low
d.Hi
Deviation High
d.Lo
Deviation Low
A1.TYP
ALARM 1 TYPE
Selects the type of alarm
bnd
Deviation band
As order 
code 
Conf
A 1 . - - -
ALARM 1 SETPOINT
Alarm 1 threshold value.
The last three characters show the type of 
alarm configured from the above list 
Instrument range
0
L3
OFF
Alarm off
A 1 . s t s
ALARM 1 OUTPUT
Indicates the status of the alarm
On
Alarm on
Read
only
A1.HYS
ALARM 1 
HYSTERESIS 
See description in manufacture manual
0 to 9999
Conf
none
Non-latching
Auto
Latching with automatic 
resetting 
Man
Latching with manual 
resetting 
A1.LAT
ALARM 1 
LATCHING TYPE 
See description in manufacture manual
Evt
Event (no alarm flashing 
beacon but messages can 
be displayed) 
As order 
code 
Conf
No
No blocking
A1.BLK
ALARM 1 
BLOCKING 
See description in manufacture manual
yes
Blocking
No
Conf
The above parameters are repeated for Alarm 2, A2; Alarm 3, A3; Alarm 4, A4
TIMER 
LIST 
‘t i m e r ’’
Name
Scrolling 
Display 
Parameter Description
Value
Default
Access 
Level 
none
Timer disabled
dwel
Dwell
deLY
Delayed switch on
SFST
Soft start
T M . C F G
TIMER 
CONFIGURAT
ION 
Timer type configuration
prog
Programmer
As order 
code 
L3
Hour
Hours
HH:MM
T M . r e s
TIMER 
RESOLUTION 
To set the time units
Min
Minutes
MM:SS
Conf
R/O
L3