1 master parameter list, Master parameter list – Sterlco Micro Series Water Temperature Control Unit User Manual
Page 13

3200 Series
ACS 3216 Operators Manual 13
7.1.1
Master Parameter List
INPUT LIST
I N P U T
Name
Scrolling Display
Parameter Description
Value
Default
Access Level
I N . T Y P
INPUT TYPE
Selects input linearisation and range
See manufacture manual for input types available
Conf
L3 R/O
none
No units - only for custom linearisation
o
C
Celsius
o
F
Fahrenheit
o
k
Kelvin
U N I T S
DISPLAY UNITS
Display units shown on the 
instrument 
PErc
%
o
C
L3
nnnn
No DP
nnn.n
One DP
D E C . P
DISPLAY 
POINTS 
Decimal point position
nn.nn
Two DP
nnnn
Conf
L3 R/O
M V . H I
LINEAR INPUT 
HIGH 
High limit for mV (mA) inputs
-10.00 to +80.00mV
80.00
Conf
M V . L o
LINEAR INPUT 
LOW 
Low limit for mV (mA) inputs
-10.00 to +80.00mV
-10.00 Conf
RNG.HI
RANGE HIGH 
LIMIT 
Range high limit for thermocouple 
RTD and mV inputs 
From the high limit of the selected input type to the 
‘Low Range Limit’ parameter minus one display unit. 
Conf
L3 R/O
RNG.LO
RANGE LOW 
LIMIT 
Range low limit for thermocouple 
RTD and mV inputs 
From the low limit of the selected input type to the 
‘High Range Limit’ parameter minus one display unit. 
Conf
L3 R/O
PV.OFS
PV OFFSET
A simple offset applied to all input 
values. 
Generally one decimal point more than PV
L3
F I L T . T
FILTER TIME
Input filter time
OFF to 100.0 seconds
1.6
L3
Auto
Automatic
0
o
C
Fixed at 0
o
C
C J . t y p
CJC TYPE
Configuration of the CJC type
50
o
C
Fixed at 50
o
C
Auto
Conf and if 
T/C 
L3 R/O
oFF
No sensor break will be detected
on
Open circuit sensor will be detected
S B . t y p
SENSOR BREAK 
TYPE 
Defines the action which is applied 
to the control output if the sensor 
breaks (open circuit). 
Lat
Latching
on
Conf
L3 R/O
C J C . i n
CJC 
TEMPERATURE 
Temperature measured at the rear 
terminal block. Used in the CJC 
calculation 
Read only
Conf
L3 R/O and 
if T/C 
P v . i n
PV INPUT 
VALUE 
Current measured temperature
Minimum display to maximum display range
Conf
L3 R/O
m v . i n
MILLIVOLT 
INPUT VALUE 
Millivolts measured at the rear PV 
Input terminals 
xx.xx mV - read only
Conf
L3 R/O
INPUT/OUTPUT LIST 1 ‘I O -1 ’
Name
Scrolling Display
Parameter Description
Value
Default
Access Level
none
No input or output fitted
dC.OP
DC output
ReLy
Relay output
L.IO
Logic Input/Output
1..i d
I/O 1 TYPE
I/O channel 1 hardware type 
defined by the hardware 
fitted 
SSR
Triac output
As 
ordered 
Read only
none
Disabled. If disabled no further 
parameters are shown 
d.out
Digital output
UP
Valve open codes VC and VP only
dwn
Valve close codes VC and VP only
Heat
Heat output
CooL
Cool output
d.in
Digital input if ‘1.i d ’ = ‘
L.IO
HEAt
Conf
w.SP
Working setpoint re-transmission
PV
Process variable re-transmission
1.FUNC
I/O 1 FUNCTION
I/O channel function.
If the instrument is ordered 
as valve positioner (codes 
VC or VP), only options 
available are , 
none,
d.out, UP, or dwn
Note: If output 1 is set to 
Up ensure the other valve 
position output is set to 
dwn and vice versa 
OP
Output power demand re-transmission
Shown if I/O 1 TYPE = 
dc.OP Retransmission 