Sterlco Micro Series Water Temperature Control Unit User Manual
Page 19

3200 Series
ACS 3216 Operators Manual 19
TIMER 
LIST 
‘t i m e r ’’
Name
Scrolling 
Display 
Parameter Description
Value
Default
Access 
Level 
T H R E S
TIMER START 
THRESHOLD 
To set the maximum deviation 
between SP and PV before the 
timer starts. 
Dwell timer and 
Programmer only 
Off or 1 to 3000 Units above and below setpoint
Off
L3
OFF
Control outputs go to zero %
DwEl
Control continues at SP1
SP2
Go to setpoint 2
E N d . T
TIMER END 
TYPE 
To determine the action which 
takes place when the timer has 
timed out. 
Dwell timer and 
Programmer only 
res
Reset programmer
Conf
S S . S P
SOFT START 
SETOINT 
Sets the threshold below which 
the power is limited 
SFST timer only
Controller input range
0
Conf
S S . P W R
SOFT START 
POWER LIMIT 
Sets the limit to the power 
output during start up 
SFST timer only
0 to 100%
0
Conf
res
Reset
run
Running (counting)
hoLd
Running (hold)
T . S T A T
TIMER 
STATUS 
Timer status
end
Timed out
L3
Sp
Starts at SP1 (or SP2).
The program must be re-started after a 
power failure. 
PV
Starts at the current Process value.
The program must be re-started after a 
power failure. 
sp.rb
Starts at SP1 (or SP2).
The program will continue to run from 
the original setpoint value at the last 
ramp rate. 
s e r v o
SERVO MODE
Defines the way in which the 
programmer starts and how it 
recovers from a power failure 
Programmer only
pv.rb
Starts at the current Process value.
The program will continue to run from 
the current process value and ramp back 
at the last ramp rate 
sp
T s p . 1
TARGET 
SETPOINT 1 
To set the target value for the 
first setpoint 
Controller input range
0
L2
R m p . 1
RAMP RATE 1
To set the rate at which the 
setpoint changes to reach 
TSP.1 
Off, 0:1 to 3000 units per min or hour
Off
L2
D w e l . 1
DWELL 1
To set the time at which the 
setpoint remains at TSP.1 
Off, 0:01 to 99:59 hh:mm or mm.ss
Off
L2
The above three parameters are repeated for the next 3 program segments, i.e. TSP.2, (3 & 4), RMP.2 (3 & 4), DWEL.2 (3 & 4)
d w e l l
SET TIMER 
DURATION 
To set the time duration (not 
programmer) 
0:00 to 99:59 hh:mm or mm.ss
0
L3
T . E L A P
ELAPSED 
TIME 
Time elapsed from when the 
timer starts to run 
0:00 to 99.59 hh:mm or mm.ss
L3 read 
only 
T . R E M N
TIME 
REMAINING 
Time remaining to reach the 
set time. 
0:00 to 99.59 hh:mm or mm.ss
L3
e v e n t
EVENT 
OUTPUTS 
Event output operates during 
the selected segment 
Programmer only
0 = No events operate in any segment
255 -= Events operate in all segments
0 L3
p . c y c l
PROGRAM 
CYCLES 
Sets the number of times that a 
program is repeated 
1 to 100
1
L3
c y c l e
PROGRAM 
CYCLE 
Displays the current cycle 
when the program is running 
1 to 100
L3
The timer can be restarted from the Reset condition by changing the time remaining parameter.
CALIBRATION PARAMETER LIST
‘cAL’