Sterlco Micro Series Water Temperature Control Unit User Manual
Page 16
3200
Series
16 ACS 3216 Operators Manual
nor
Normal
4.SENS
SENSE
To configure the polarity of
output channel 4
Inv
Inverted
nor
Conf
LOGIC INPUT LIST ‘l a ’ / ‘LB’
Name
Scrolling Display
Parameter Description
Value
Default
Access Level
L.TYPE
LOGIC INPUT
TYPE
Input channel type
L.IP
Logic input
As order
code
Conf
Read only
none
Input not used
Ac.AL
Alarm acknowledge
SP2
Setpoint 2 select
Loc.b
Front keypad disable
t.res
Timer/programmer reset
t.run
Timer/programmer run
t.rrS
Timer/programmer run/reset. Make to
run, break to reset
t.HLd
Timer/programmer hold
Man
Manual status
Sby
Standby mode. In this mode control
outputs go to zero demand
rmt
To allow a remote setpoint to be
selected through the LA digital input.
rec
Recipe select through IO1 digital
input
UP
Remote key ‘Up’
L.d.i n
LOGIC INPUT
FUNCTION
To configure the function of the
digital input
dwn
Remote key ‘Down’
Ac.AL
Conf
nor
Normal
Inv
Inverted
L.SENS
LOGIC INPUT
SENSE
To configure the polarity of the
input channel
4.20
4-20mA output
nor
Conf
SETPOINT LIST ‘SP’
Name
Scrolling Display
Parameter Description
Value
Default
Access Level
SP1
Setpoint 1 selected
S P . S E L
SETPOINT
SELECT
This enables the main or secondary
setpoint to be selected form the front
panel buttons
SP2
Setpoint 2 selected
SP1
L3
S P 1
SETPOINT 1
Main or normally selected setpoint
Low to high setpoint limits
0
L3
S P 2
SETPOINT 2
Secondary or standby setpoint
Low to high setpoint limits
0
L3
S P . H I
SETPOINT HIGH
LIMIT
Maximum allowable setpoint setting
Setpoint low limit (SP.LO) to high range
limit. Also limited by the rng.hi and
rng.lo parameters
Range
High Limit
L3
S P . L O
SETPOINT LOW
LIMIT
Minimum allowable setpoint setting
Low range limit to Setpoint high limit
(SP.HI). Also limited by the rng.hi and
rng.lo parameters
Range
Low Limit
L3
r E m . s p
REMOTE
SETPOINT
Reads the current remote setpoint value
when remote setpoint is in use
Read only
No
Not selected
l - r
REMOTE
SETPOINT
SELECT
To select the remote digital
communications setpoint
YES
Selected
no
Conf
S P . R A T
SETPOINT RATE
LIMIT
Limits the rate of change of the setpoint.
Operates on both SP1 and SP2
Step change (
OFF) or 0.1 to 3000
display units per minute.
Resolution one decimal place more than
PV
Off
L3
min
Minutes
Hour
Hours
r a m p u
SETPOINT RAMP
UNITS
To set the units for the setpoint rate limit
SEC
Seconds
min
L3
l o c . t
LOCAL SETPOINT
TRIM
To apply a fixed offset to the setpoint in
use
-199.9 to 300.0
0.0
L3
R E M . H I
REMOTE INPUT
HIGH SCALAR
Sets the maximum scale limit for the
remote setpoint
R E M . l o
REMOTE INPUT
LOW SCALAR
Seta the minimum scale limit for the
remote setpoint
Between Range High and Low Limits
L3