2 processing, Processing – Sterlco Micro Series Water Temperature Control Unit User Manual
Page 27
3200 Series
ACS 3216 Operators Manual 27
STATUS PROCESS
POLL:
20 40
SELECT:
N/A
FORMAT:
16 Bits
UNITS:
None
DESCRIPTION:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Processing
Alarm, System
Alarm,
Process
N/A
Alarm, High Temp
Alarm, Low Temp
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
9.5.2
PROCESSI
NG
BIT#:
0
DESCRIPTION:
This status bit states whether this unit is currently processing.
0 = not currently processing (3200 manual mode)
1 = processing (3200 auto mode)
ALARM, SYSTEM
BIT#:
1
DESCRIPTION:
This status bit states an alarm is present. In the 3200, this is set if any of the 4 temperature alarms are set, or
if Sensor Break, Span Error, or Loop break is set.
ALARM, PROCESS
BIT#
2
DESCRIPTION:
This bit indicates that an alarm that affects the process has occurred. In the 3200, this is set if any of the 4
alarms are set, or if Sensor Break, Span Error, or Loop break is set.