3 navigation diagram, Custom scrolling text, Custom configurations – Sterlco Micro Series Water Temperature Control Unit User Manual
Page 12: Navigation diagram
3200
Series
12 ACS 3216 Operators Manual
6.3
Navigation Diagram
The diagram below shows the all list headings available in configuration level for 3216 controllers.
The parameters in a list are shown in tables in the following sections of this manual together with explanations of their meanings
and possible use.
7. Custom Scrolling Text
The 3216 has custom scrolling text used to provide detailed information about the status of the process. The scrolling text will
appear in the lower readout of the display. The following is a list of custom scrolling text messages used.
Controller
Scrolling Display
Description
Water Unit (TCU)
VENTING IN PROCESS
On power up, the vent valve opens for 60 seconds to allow air to
bleed out of the system. This text displays for the 60seconds.
1 Compressor Chiller
COMPRESSOR ON
This text displays when the compressor turns on. It will remain
on until the compressor turns off.
1 Compressor Chiller
COMPRESSOR OFF
This text displays when the compressor turns off. It will remain
on until the compressor turns on.
2 Compressor Chiller
COMPRESSOR A ON
COMPRESSOR B ON
This text displays when either or both compressors are on. It will
remain on until either or both compressors turn off.
Custom Configurations
See Appendix B for tables summarizing the parameter values for each of the custom configurations.
Configuration
IO1 LIST
Output 2
List
AA Relay
List
Logic Input
a List
PROCESS
INPUT
LIST
current
transformer
List
Control
List
Recipe
List
Comms List
Timer
List
Alarms
List
Setpoint
List
Calibration
List
Access
List
Sensor Input
Output 1 or
Input 1
Output 2
AA Relay
(Output 4)
Digital Input
CT Input
Calibration
Communications
Timer
Alarm
Control
Setpoint
Access
Recipe
Level 2
Parameters