7

Operation

7.1 Minimum load requirements for the HF43 with voltage outputs


The following requirements apply to any external device or circuit connected to the HF43 transmitter with
voltage outputs:



















In the situation where the external device uses an internal pull-up resistor the value of this resistor should
meet the requirements shown below. It is also necessary to add a pull-down resistor RL connected to ground
in order to be able to read 100% of the range of the HF43 voltage output.




















7.2 HF42 and HF43 transmitters (analog outputs)

If so desired, use the HW4 software to configure the HF4. Complete the mechanical and electrical installation
and simply power up the HF4.

HF43 output signal

Input resistance RL

0…1V

>=1kOhm

0…5V

>=5kOhm

0…10V

>=10kOhm

HF43 signal

VCC

R pull-up

RL

0…1V

3.3V

≥ 250 kOhm

1 kOhm

HF43 signal

VCC

R pull-up

RL

0…1V

5.0V

≥ 400 kOhm

1 kOhm

0…5V

5.0V

≥ 400 kOhm

5 kOhm

HF43 signal

VCC

R pull-up

RL

0…1V

10.0V

≥ 1 MOhm

1 kOhm

0…5V

10.0V

≥ 1 MOhm

5 kOhm

0…10V

10.0V

≥ 1 MOhm

10 kOhm

RL

GND

HF43

Voltage Output

R Pull-up

RL

GND

VCC

HF43

Voltage Output