5 as interface bus connection – NORD Drivesystems BU0100 User Manual
Page 28

Technical data SK 1xxE
28
Technical modifications observed
BU 0100 GB
5.5 AS interface bus connection
The AS1 module (4 inputs / 4 outputs) corresponds to the requirements of the new AS interface according to
specification 2.1. As with the control electronics of the SK 1xxE, this assembly is entirely powered by the AS
interface. The inputs and outputs are resistant to short circuit and overload
A watchdog function has been integrated that switches the outputs current less if no communication takes
place on the AS interface line.
Up to 3 circuit elements can be queried with the inputs. A signal lamp can be activated by the output whereby
the energy is supplied from the AS interface system. The assignment for the control signals of the SK 1xxE is
included in the table below. Apart from the motor activation, up to 3 additional sensors can be connected to
M12 sockets and read. Together, they may draw max. 130 mA current.
AS1 Assignment
of M12 socket for AS Interface
Pin 1
AS1 +
Pin 2
-
Pin 3
AS1 -
Pin 4
-
Probe assignment of
the M12 sockets:
Probe connection 1
Probe connection 2
Pin 1
+24 VDC
+24 VDC
Pin 2
Probe input 3
---
Pin 3
GND
GND
Pin 4
Probe input 1
Probe input 2
Technical data
No-load current draw (Inputs = 0, Outputs = 0)
≤ 20 mA
Switching threshold of inputs
≤ 0.8 mA (low)
≥ 5 mA (high)
Voltage 20-30
VDC
Outputs 4,
electronic
Load capacity
100 mA per output, 24 VDC
(Sum of all outputs < 180 mA)
Length of power cable
E/A: max. 1.5m
Operating voltage
Via AS Interface
Operating current
< 200 mA
EMC compliance with
EN 50 081-2, EN 50 082-2
The AS1 Module 4E/4A has the following assignment:
AS Interface
Input
Ausgang
Bit 0
[OK] Output
[RUN-RIGHT] Input
Bit 1
Probe 3
[RUN-LEFT] Input
Bit 2
Probe 1
-
Bit 3