Functional safety with NORD SK 500E frequency inverters

46

BU 0530 GB-3712

6.4 ISO 13849-1:2006

(German version EN ISO 13849-1:2008)
For the safety-relevant stop functions STO and SS1 (designation as per IEC 61800-5-2:2007), frequency
inverters with the safe shut-down methods "safe pulse block" and "switch-off of the 24 V supply" fulfil the
requirements for Performance Level e. Safety category 4 can not be achieved.

Shut-down method

“Safe pulse block”

PL

e

DC

cannot be established (PFH=0)

MTTF

d

"high" (>100 years)

T

M

20 years

Category

4


PL

Performance Level

DC

Diagnostic coverage level

MTTF

d

The mean time until a hazardous failure

T

M

Period of use



The digital inputs which are used for the implementation of safety-relevant stop functions are primarily intended
as auxiliary inputs and can fulfil the requirements of Safety Category 1 and Performance Level c.

Input

DIN 1 to DIN 4

PL

c

DC

No DC

PFH

588.39 FIT

MTTF

d

"high" (>100 years)

T

M

20 years

Category

1


NOTE

The values given only refer to the stated inputs or shut-down methods

The components which are additionally required for the implementation of a safety
function, such as a protective switching device, an emergency stop button etc. must also
be taken into account for the evaluation of the safety function. The resulting safety-relevant
data can be significantly influenced by these components.