4 Parameterisation
BU 0530 GB-3712
43
List of the functions or the digital inputs P420 ... P425, P470 which are relevant to "Functional safety"
Value Function
Description
Signal
00
No function
Input switched off.
-----
10
Disable voltage
7
The FI output voltage is switched off; the motor runs down freely.
Low
11
Fast stop
³
The FI reduces the frequency according to the programmed fast stop time
P426.
Low
List of possible functions for the relays and digital outputs P434, P441, P450, P455
Valu
e
Function
Description
Signal*
00
No function
Input switched off.
Low
01
External brake
For the control of a mechanical brake on the motor. The relay switches at
a programmed absolute minimum frequency (P505). For typical brakes a
setpoint delay of 0.2 … 0.3 seconds (see also P107) should be
programmed.
A mechanical brake can be directly AC switched. (Please note the tech-
nical specifications of the relay contacts)
High
07
Fault
General fault message, fault is active or not yet acknowledged.
Error
– contact opens
(ready
– contact closes)
Low
39
STO inactive
The relay / bit deactivates if STO or the Safe Stop are active.
High
* For relay contacts (High = "Contact closed", Low = "Contact open")
A complete list of all possible functions can be found in Manual BU 0500 GB.
7
Also effective for bus control (RS232, RS485, CANbus, CANopen, DeviceNet, Profibus, InterBus, AS-Interface)