NORD Drivesystems BU0530 User Manual
Page 35
3 Assembly and installation
BU 0530 GB-3712
35
Relevance
SK 500E
SK 505E
SK 510E
SK 511E
SK 515E
SK 520E
SK 530E
SK 535E
SK 540E
SK 545E
√
√
√
Terminals X5:
21
22
23
24
25
44*
40
41
*
Terminal
44:
up to Size 4: VI
Size 5 and above:
VO
DIN1
DIN2
DIN3
DIN4
DIN5
V…
24V
GND /
0V
VO 5V
Designation
Terminal Function
[factory setting]
Data
Description / wiring suggestion
Parameter
up to
SK 535E
21
Digital input 1
[ON right]
7.5...30V, R
i
=6.1k
Not suitable for
thermistor evaluation.
HTL encoders can
only be connected to
DIN2 and DIN4
Limiting frequencies:
max.
10 kHz
min.
15 Hz
Each digital input has a reaction
time of ≤ 5ms.
21
22
23
24
25
44
40
41
18
… 30V
motor - PTC
GND / 0V
P420
22
Digital input 2
[ON left]
P421
23
Digital input 3
[parameter set bit0]
P422
24
Digital input 4
[Fixed frequency 1,
P429]
P423
25
Digital input 5
[no function]
Only S1
– S4
2.5...30V, R
i
=2.2k
Not suitable for
evaluation of a safety
device.
Suitable for thermistor
evaluation with 5V.
NOTE: For the motor
thermistor P424 = 13
must be set.
Above Size 5
Thermistor on
X13:T1/T2
P424
44
Size 1 to Size 4
VI 24V supply
voltage input
18…30V
at least 800mA (input)
Voltage supply for the FI control unit.
This is essential for the function of
the frequency inverter.
Size 5 and above
VO 24V supply
voltageoutput
24V ± 25%
max. 200mA (output)
Supply voltage provided by the
frequency inverter for connection to
the digital inputs or the supply of a
10-30V encoder.
The 24V control voltage is
generated by the FI, however it can
also be supplied via the terminals
X12:44/40. Supply via terminal
X5:44 is not possible.
40
Reference potential
for digital signals
0V digital
Reference potential
41
5V supply voltage
output
5V
20%
Voltage supply for motor-PTC