Terminal block x5 – digital in – NORD Drivesystems BU0530 User Manual
Page 34
Functional safety with NORD SK 500E frequency inverters
34
BU 0530 GB-3712
3.4.4
Details of the "Digital inputs" control connections
NOTE
AGND and DGND are common reference potentials for analog or digital inputs.
5V / 15V can be collected by several terminals if required. The sum of collected currents must
not exceed 250mA / 150mA.
Terminal block X5
– Digital In
Relevance
SK 500E
SK 505E
SK 510E
SK 511E
SK 515E
SK 520E
SK 530E
SK 535E
SK 540E
SK 545E
√
√
√
√
√
Terminals X5:
21
22
23
24
25
42
40
41
DIN1
DIN2
DIN3
DIN4
DIN5
VO 15V
GND / 0V
VO 5V
Designation
Terminal Function
[factory setting]
Data
Description / wiring suggestion
Parameter
up to
SK
535E
21
Digital input 1
[ON right]
7.5...30V, R
i
=6.1k
Not suitable for
thermistor evaluation.
HTL encoders can only
be connected to DIN2
and DIN4
Limiting frequencies:
max.
10 kHz
min.
15 Hz
Each digital input has a reaction time
o
f ≤ 5ms.
Control with internal 15V:
21
22
23
24
25
42
40
41
15V
motor - PTC
Control with external 7.5-30V:
21
22
23
24
25
42
40
41
7.5
… 30V
motor - PTC
GND / 0V
P420
22
Digital input 2
[ON left]
P421
23
Digital input 3
[parameter set bit0]
P422
24
Digital input 4
[Fixed frequency 1,
P429]
P423
25
Digital input 5
[no function]
2.5...30V, R
i
=2.2k
Not suitable for
evaluation of a safety
device.
Suitable for thermistor
evaluation with 5V.
NOTE: For the motor
thermistor P424 = 13
must be set.
P424
42
15V supply voltage
output
15V
20%
Supply voltage provided by the
frequency inverter for connection to
the digital inputs or the supply of a
10-30V encoder.
40
Reference potential
for digital signals
0V digital
Reference potential
41
5V supply voltage
output
5V
20%
Voltage supply for motor-PTC