Alarm 2 function: Select

0FF

,

Lo

,

Hi

,

HiLo

,

SF

,

0t

, or

SF0t

. Factory default is

Lo

.

0FF

Alarm 2 is disabled. No Alarm 2 menu items appear in the
Secondary or Secure menus.

Lo

Low Alarm Only.

A2Lo

appears in the Secondary Menu.

Hi

High Alarm Only.

A2Hi

appears in the Secondary Menu.

HiLo

High and Low Alarms. Both

A2Lo

and

A2Hi

appear in the Secondary

Menu, and share the same Alarm 2 Relay output.

SF

Seal Failure ONLY will trigger Alarm.

0t

Over Temperature Failure ONLY will trigger Alarm

SF0t

Both Seal Failure and Over Temperature Failure will trigger Alarm.

With the Alarm Function settings on

0FF

,

SF

,

0t

,

SF0t

certain alarm related menu items

will disappear as those menu items do not apply.

A2t

Alarm 2 Type: Select

AbS

or

dE

. Factory default is

AbS

.

AbS

Absolute Alarm that may be set anywhere within the values of

SCAL

and

SCAH

and is independent of

SP1H

.

dE

Deviation Alarm that may be set as an offset from

SP1H

. As

SP1H

is changed the Alarm Point will track with

SP1H

.

A2rE

Alarm 2 Reset: Select

0n0F

or

HoLd

Factory default is

0n0F

.

0n0F

Automatic Reset.

HoLd

Manual Reset. Reset (acknowledge) by simultaneously pressing the

INDEX & DOWN ARROW keys for 5 seconds.

A2Pi

Alarm 2 Power Interrupt: Select

0n

or

0FF

. Factory default is

0FF

.

0n

Alarm Power Interrupt is On.

0FF

Alarm Power Interrupt is OFF.

A2iH

Alarm 2 Inhibit: Select

0n

or

0FF

. Factory default is

0FF

.

0n

Alarm Inhibit is On. Alarm action is suspended until the process
value first enters a non-alarm condition.

0FF

Alarm Inhibit is OFF.

A2St

Alarm 2 Output State: Select

CL0S

or

0PEn

. Factory default is

CL0S

.

CL0S

Closes Contacts at Alarm Set Point.

0PEn

Opens Contacts at Alarm Set Point.

A2LP

Alarm 2 Lamp: Select

0 on

or

0oFF

. Factory default is

0 on

.

0 on

Alarm Lamp is ON when alarm contact is closed.

0oFF

Alarm Lamp is OFF when alarm contact is closed.

A2td

Alarm 2 time Delay: Select

0FF

or

1 to 8000

seconds. Factory default is

0FF

.

0FF

Alarm function will operate when triggered at programmed Alarm

Set Point.

1-8000

Alarm function will only operate once the programmed time has

elapsed after the alarm was triggered by the Alarm Set Point.