In the Secure menu the value of

PSF

is programmed for the action of the MPC based on

the condition of a seal failure. If set to ˝

AUt0

˝ when pump moisture sensor indicates that

there is a seal failure condition then the corresponding pump seal failure lamp is lit on the
controller. The pump will remain in service with only the lamp indication of failure. The
lamp will be turned off automatically when the seal failure condition has ceased.

If

PSF

is set to ˝

rES

˝ when pump moisture sensor indicates that there is a seal failure

condition then the corresponding pump seal failure lamp is lit on the controller. If the MPC
is only being used with one pump or being used with two pumps with the lead/lag function
turned off then no action is taken by the MPC with the operation of the pumps. The failure
indication lamp will be manually reset as described in the next paragraph. If the MPC is
being used with two pumps with the lead/lag function turned on then the failed pump will
automatically become the lag pump, the remaining pump will become the lead pump, and
the alternation will be discontinued. The lamp indication and pump alternation can be
manually reset as described in the next paragraph.

Once the pump has been repaired the seal failure action can be reset with the values of

P1SF

and

P2SF

in the Secondary menu. The item

P1SF

or

P2SF

will display

FA1L

if the

corresponding pump has met the condition of a seal failure. Press the ENTER key to
reset. If the pump moisture sensor is still in the fail condition then the control will not reset.
If the moisture sensor is no longer in the fail condition then the display will revert to ˝----˝.

OVER TEMPERATURE OPERATION
Most pumps have an installed normally closed thermostat for over temperature protection
of the pump. The thermostat has a preset value from the pump manufacturer at which
point the pump needs to be shut down. The Mercoid

®

MPC detects when the thermostat

signal changes to open and shuts down the pump.

In the Secure menu the value of

P0t

is programmed for the action of the MPC based on the

condition of the over temperature. When the pump temperature sensor indicates that there
is an over temperature condition the pump will be held out of service and the corresponding
pump over temperature lamp is lit on the controller. If using the MPC with two pumps with
the lead/lag function turned on then the failed pump will automatically be taken out of
service, the remaining pump will become the lead pump, and the alternation will be
discontinued. When controlling two pumps with the lead/lag function off the failed pump will
automatically be taken out of service and the remaining pump will be controlled by the

SP1H

and

SP1L

set points.

If

P0t

is set to ˝

AUt0

˝ then the pump will be automatically placed back into service and

the lamp turned off when the over temperature condition has ceased. If set to ˝

rES

˝ then

the pump will remain out of service and the lamp lit until the corresponding manual reset

P10t

or

P20t

is reset in the Secondary menu (described in the next paragraph). The pump

cannot be brought back into service until the over temperature condition has ceased.

Once the pump has cooled down the MPC Pump Controller can be reset with the values of

P10t

and

P20t

in the Secondary menu. The item

P10t

or

P20t

will display

FA1L

if the

pump has met the condition of over temperature. Press the ENTER key to reset. If the
pump temperature sensor is still in the fail condition then the control will not reset. If the
temperature input is no longer in the fail condition then the display will revert to ˝----˝.