MENU SELECTIONS
Notation Conventions for the Menus
Because of the number of features available in this control, information is included that
may not apply to your specific control. All usable features are included in this book, but
may not be used in your process. To increase clarity the following conventions are used:

1. Certain features or functions shown in this book are contextual. This means that Menu
Items may or may not appear, depending on other Menu Item selections. Whenever this
occurs, a notation is made in the Menu Item that ˝controls˝ or ˝directs˝ other menu items. If
you are looking for a particular menu item and can't find it, check the menu item that is its
˝control˝ for proper setting.
2. The ˝#˝ symbol is used in two ways. It is used inside a group of characters to indicate
which set point function (SP1 or SP2) is being affected. It is also used before a group of
characters of a menu item to indicate that there may be more than one selection or value
for that menu item.

Secondary Menu

Press the INDEX key for 2 seconds to start the menu. Press INDEX to advance

to the next menu item. Press UP ARROW or DOWN ARROW

to change the value in the display. Press ENTER to retain the value.

SP1H

Pump 1 On Set Point. Factory Default

23.1

(feet).

SP1L

Pump 1 Off Set Point. Factory Default

0.0

(feet).

SP2H

Pump 2 On Set Point. Factory Default

23.1

(feet).

SP2L

Pump 2 Off Set Point. Factory Default

0.0

(feet).

A1Hi

Alarm 1 High: Factory Default

23.1

(feet).

A2Lo

Alarm 2 Low: Factory Default

2.0

(feet).

SFS1

Pump 1 Seal Failure Set Point: Select 10 to 500 in any increment of 10.

Sets the resistance set point at which the controller will trip the Seal Failure

based on the input from the pump moisture sensor. The controller will
activate the Seal Failure condition based on a decrease of resistance to the
set point. Selectable resistance range is from 10K to 500K ohms with the
factory default at 120K ohms.

SFS2

Pump 2 Seal Failure Set Point: Select 10 to 500 in any increment of 10.
Sets the resistance set point at which the controller will trip the Seal Failure
based on the input from the pump moisture sensor. The controller will
activate the Seal Failure condition based on a decrease of resistance to the
set point. Selectable resistance range is from 10K to 500K ohms with the
factory default at 120K ohms.