P1rn

Pump 1 Run Time: Total ON Time for Pump 1 in HOURS since last reset
(0000 - 9999 hours).

P2rn

Pump 2 Run Time: Total ON Time for Pump 2 in HOURS since last reset
(0000 - 9999 hours).

P1SF

Pump 1 Reset for Seal Failure. Displays ˝----˝ when pump 1 is in normal operating
condition based on seal failure input. Displays

FA1L

if pump 1 has met the

condition of a seal failure. Press the ENTER key to reset. If pump 1 seal
failure is still in the fail condition then the control will not reset. If the seal failure
input is no longer in fail condition then the display will revert to ˝----˝.

P2SF

Pump 2 Reset for Seal Failure. Displays ˝----˝ when pump 2 is in normal operating
condition based on seal failure input. Displays

FA1L

if pump 2 has met the condi-

tion of seal failure. Press the ENTER key to reset. If pump 2 seal failure is
still in the fail condition then the control will not reset. If the seal failure input is no
longer in fail condition then the display will revert to ˝----˝.

P10t

Pump 1 Reset for Over Temperature. Displays ˝----˝ when pump 1 is in normal
operating condition based on temperature input. Displays

FA1L

if pump 1 has met

the condition of over temperature. Press the ENTER key to reset. If pump 1

temperature input is still in the fail condition then the control will not reset. If the
temperature input is no longer in fail condition then the display will revert to ˝----˝.

P20t

Pump 2 Reset for Over Temperature. Displays ˝----˝ when pump 2 is in normal
operating condition based on temperature input. Displays

FA1L

if pump 2 has me

the condition of over temperature. Press the ENTER key to reset. If pump 2

temperature input is still in the fail condition then the control will not reset. If the
temperature input is no longer in fail condition then the display will revert to ˝----˝.