beautypg.com

Page 5 – Dwyer AFG User Manual

Page 5

background image

Calibration on Site:
To achieve the best possible accuracy, the AFG Flow Grids must
be calibrated on site and the following method of site calibration
and subsequent calculation is advised.

Any valid method of determining the volume flow rate may be used
in establishing the flow rate to differential pressure characteristic.

The following method and theory applies to the use of Pitot static
tubes, as the primary means of determining volume flow rate by
the velocity traverse technique.

To calibrate an AFG Flow Grid:
1. Install the AFG Flow Grid as described (See installation pages 2
& 3) and connect to a suitable manometer.

2. Prepare holes in the duct wall upstream of the AFG Flow Grid
for the Pitot static tube traverse to give an adequate survey of the
duct velocity pattern and mean duct velocity.

3. Operate the system to give a typical flow rate through the Flow
Grid and take records of Pitot static tube traverse readings and the
Flow Grid differential pressure readings.

4. If possible, arrange the system flow rate to be changed to give
additional sets of readings covering the range over which the sys-
tem is intended to be used.

5. The theory of the AFG Flow Grid for normal atmosphere condi-
tions is shown on page 4.

(Δp)/(Pv)= M (See page 4).

Measure the ambient temperature ‘t’, the ambient barometric
pressure ‘B’ and the duct static pressure Ps. Calculate the cor-
rection factor CF in the appropriate units.

Hence calculate the flow constant ‘K’ for each set of readings
taken.

Table 5: Calculating Flow Constant K

6. Suggested format for results using worked examples:

Metric Units (example- using AFG Flow Grid in duct size 250 mm
x 500 mm)

Table 6: Example: K Factor Calculation (Metric)

Table 7: Graph Plotting Information Derived from Traverse
Data (metric)

Imperial Units (example- using AFG Flow Grid in duct size 10” x
20”)

Table 8: Example: K Factor Calculation (Imperial)

Table 9: Graph Plotting Information Derived from Traverse
Data (Imperial)

(see Fig. 17 for Graph)

page 5

Where =
Δp = X Flowgrid differential pressure
M = X Flow grid magnification factor
Pv = duct mean velocity pressure Pa
A = cross section area of duct m

2

CF = correction factor
Take the average K

1

and plot the

curve of Q v Δp

Where
Q = K

1

Δp

Q = volume flowrate m

3

/s

Δp = X Flowgrid differential pressure in. wg.
M = X Flowgrid magnification factor
Pv = duct mean velocity pressure wg
A = cross section area of duct ft

2

CF = correction factor

Q = K

1

Δp

Q = volume flowrate ft

3

/min

K

1

= A x 1.291 CF

M

K

1

= A x 4005 CF

M

SI Units

Imperial Units

1

250

15.81

96

9.80

48

6.93

2

230

15.17

92

9.59

46

6.78

3

260

16.12

99

9.95

47

6.86

4

240

15.49

96

9.80

51

7.14

5

212

14.56

90

9.49

45

6.71

Reading

No.

Pitot Tube Traverse

Readings Pv Pa

& Pv

Average

of

Pv

Flow-

grid

Diff

Δp

Mag-
Factor
Δp = M
Pv

PITOT STATIC TUBE TRAVERSE DATA

Average

of

Pv

Flow
Constant
K1 =
Ax1.291

CF

M

Pv

Pv

Pv

Pv

Pv

Pv

15.43

9.73

6.88

238.08

94.67

47.33

514.2

199.8

98.1

2.160

2.110

2.072

0.1095

0.1108

0.1118

DUCT AREA A = 250 X 500 mm = 0.125 m

2

AVERAGE k

1

= 0.1107

1

0.95

0.975

0.48

0.693

0.23

0.480

2

0.99

0.995

0.50

0.707

0.25

0.50

3

1.03

1.015

0.52

0.721

0.25

0.50

4

1.06

1.030

0.53

0.728

0.24

0.49

5

0.99

0.996

0.49

0.70

0.22

0.469

Reading

No.

Pitot Tube Traverse

Readings Pv Pa

& Pv

Average

of

Pv

Flow-

grid

Diff

Δp

Mag-
Factor
Δp = M
Pv

PITOT STATIC TUBE TRAVERSE DATA

Average

of

Pv

Flow
Constant
K1 =
Ax4005

CF

M

Pv

Pv

Pv

Pv

Pv

Pv

1.002

0.710

0.488

1.004

0.504

0.238

2.169

1.063

0.493

2.160

2.110

2.072

3781

3828

3863

DUCT AREA A = 10˝ X 20˝ = 1.388 ft

2

AVERAGE k

1

= 3824

25

5

0.553

50

7.07

0.783

100

10

1.107

200

14.14

1.565

300

17.32

1.917

400

20.0

2.214

500

22.36

2.475

600

24.43

2.704

MX Flow Grid

Diff Δp Pa

Δp

Vol Flow

Rate

Q = K

1

ΔpM

3

/s

0.5

0.707

2703

1.0

1.0

3824

1.5

1.225

4684

2.0

1.414

5408

2.5

1.581

6046

MX Flow Grid

Diff Δp Pa

Δp

Vol Flow

Rate

Q = K

1

Δpft

3

/min

AFG iom1 1/3/06 2:00 PM Page 5