Badger Meter 3050 Series Btu Monitor User Manual
Page 9

Page 9
6-11
Installation & Operation Manual
Flow Sensor Wiring
The Series 3050 flow sensor inputs are extremely versatile, designed to accept either two-wire or three-wire pulse inputs
(Data Industrial 200 Series, SDI or 4000 Series) or Analog inputs. Although different rear panel terminals are used, all
parameters are set with the LCD/keypad interface. There are no internal or external jumpers, switches or potentiometers to
move or adjust.
The following pulse input types are accommodated.
•
Pulse-DI: Used for all Badger Meter Data Industrial Flow Sensors. Provides an internal pull-up resistor and uses “K”
and “Offset” values for calibration.
•
Pulse–K Factor: Accepts non zero-crossing inputs but provides no internal pull-up, classical “K” ( pulses/gallon)
values for calibration.
•
Pull-up-K Factor: Provides an internal pull-up resistor and uses classical “K” ( pulses/gallon) values for calibration.
NOTE: All the above pulse input types wire the same as shown in Figure 4. See the Programming Flow Chart on
page 18 for required input configuration.
1 ANALOG IN+
2 ANALOG IN-
3 SHIELD
4 SENSOR IN
5 GND
6 SHIELD
7 SENSOR PWR
Figure 4: Data Industrial Flow Sensor Wiring Examples (Two- and Three-Wire Pulse Types)