Dimensions / weights / positioning - vertical, Installation data, Condensers – Airedale Air Cooled Condensers R410A User Manual
Page 9: Important, Standard condenser fan (cr12 - cr30 shown)

Condensers
CR12
– CR105
Condensers
9
Installation & Maintenance : 6680953 V1.2.0 02/2013
Installation Data
DIMENSIONS / WEIGHTS / POSITIONING - VERTICAL
IMPORTANT
The following information is for general guidance; refer to the certified drawings provided
for installation.
The following illustrations show the unit following fixing leg re-orientation, instructions are
provided for this at delivery.
Standard Condenser Fan (CR12 - CR30 Shown)
3000
(2)
(1)
D
A
B
(6)
(3)
(1)
C
E
(5b)
(4)
(5a)
500
(2)
500
(2)
500
(2)
500
(2)
Diagram illustrated in mm
(1)
Airflow
(2)
Minimum clearances
(3)
12.7mm fixing hole
(4)
Mains electric isolator
(5)
Service connections to left hand side of the unit:
a = Liquid outlet
b = Discharge gas inlet
(6)
40mm lifting holes
Optional Short Case Axial Fan (SCAF) (CR80 - CR105 Shown)
3000
(2)
C
E
(5b)
(4)
(5a)
(1)
D
A
B
(6)
(3)
(1)
D
(1)
(1)
500
(2)
500
(2)
500
(2)
500
(2)
(7)
Diagram illustrated in mm
(1)
Airflow
(2)
Minimum clearances
(3)
12.7mm fixing hole
(4)
Mains electric isolator
(5)
Service connections to left hand side of the unit:
a = Liquid outlet
b = Discharge gas inlet
(6)
40mm lifting holes
(7)
Optional short case axial fan with integral duct fixing holes
DIMENSIONS (mm)
WEIGHTS (kg)
Standard Fan
Fan Options
Standard
ac Fan
Optional
EC Fan
Optional
SCAF
SCAF
EC
A
B
C
D
E
B
B
CR12
907
1076
972
847
912
1080
1065
62
67
67
CR16
907
1076
972
847
912
1080
1065
70
76
75
CR22
1102
1090
1167
1042
1107
1130
1127
77
83
88
CR30
1102
1090
1167
1042
1107
1130
1127
90
96
101
CR50
2184
1090
1167
2124
1107
1130
1127
132
145
154
CR65
2184
1090
1167
2124
1107
1130
1127
162
175
184
CR80
3565
1090
1167
1753
1107
1130
1127
208
228
242
CR105
3565
1090
1167
1753
1107
1130
1127
260
280
294