Installation Data
RE-ORIENTATION TO VERTICAL DISCHARGE
1
Remove the fixings securing the unit to the pallet.
2
In line with horizontal discharge lifting
instructions, lift the unit sufficiently to gain
access to the lower leg fixings as shown in
Fig 1.
Fig 1
3
Reposition and secure the lower 2 legs to the corner of the unit using the fixings and hole positions provided to both
faces, as Fig 2.
Note, model sizes CR80 & CR105 have an additional mid support leg, this should also be adjusted and
secured.
Fig 2
4
Lower and rest the unit down to floor and reposition and secure the upper legs as described in Step 3.
5
In line with vertical discharge lifting
instructions lift the unit slowly into vertical
orientation as Fig 3.
Fig 3
Care should be taken to ensure the unit does not drop into position and that damage is not sustained
prior to lifting the unit into final position.
6
The unit may be lifted into its final position.