Installation data, Dimensions / weights / positioning - horizontal, Installation – Airedale Air Cooled Condensers R410A User Manual
Page 8: Data, Condensers, Important, Standard condenser fan (cr12 - cr30 shown), Caution

CR12
– CR105
Condensers
8
Condensers
Installation & Maintenance : 6680953 V1.2.0 02/2013
Installation Data
DIMENSIONS / WEIGHTS / POSITIONING - HORIZONTAL
IMPORTANT
The following information is for general guidance; refer to the certified drawings provided
for installation.
The legs attached to the top of the unit are for lifting and stacking and may be removed and
stored safely if not required.
Only 2 units may be stacked together.
Standard Condenser Fan (CR12 - CR30 Shown)
3000
(2)
A
D
B
(5a)
(4)
500
(2)
500
(2)
500
(2)
(1)
(1)
(1)
C
E
(1)
150
150
(5b)
(3)
(6)
(7)
Diagram illustrated in mm
(1)
Airflow
(2)
Minimum clearances
(3)
12.7mm fixing hole
(4)
Mains electric isolator
(5)
Service connections to left hand side of the unit:
a = Discharge gas inlet (ALWAYS above (b))
b = Liquid outlet
(6)
Top brackets may be used to secure unit of similar size
on top, using, 2 x 12.7mm fixing holes
(7)
40mm lifting holes
Optional Short Case Axial Fan (SCAF) (CR80 - CR105 Shown)
3000
(2)
A
D
B
(5b)
(4)
500
(2)
500
(2)
500
(2)
(1)
(1)
(1)
C
E
(1)
150
150
(6)
(3)
D
(1)
(1)
(5a)
(8)
(7)
Diagram illustrated in mm
(1)
Airflow
(2)
Minimum clearances
(3)
12.7mm fixing hole
(4)
Mains electric isolator
(5)
Service connections to left hand side of the unit:
a = Discharge gas inlet (ALWAYS above (b))
b = Liquid outlet
(6)
Top brackets may be used to secure unit of similar size
on top, using, 2 x 12.7mm fixing holes
(7)
40mm lifting holes
(8)
Optional Short Case Axial Fan with integral duct fixing
holes
DIMENSIONS (mm)
WEIGHTS (kg)
Standard Fan
Standard
Fan
Optional
EC Fan
Optional
SCAF
A
B
C
D
E
CR12
907
972
1000
845
700
62
67
67
CR16
907
972
1000
845
700
70
76
75
CR22
1102
1167
1000
1040
700
77
83
88
CR30
1102
1167
1000
1040
700
90
96
101
CR50
2184
1167
1000
2121
700
132
145
154
CR65
2184
1167
1000
2121
700
162
175
184
CR80
3565
1167
1000
1752
700
208
228
242
CR105
3565
1167
1000
1752
700
260
280
294
CAUTION
A vertical air discharge unit is recommended for installation in windy locations or wherever a
horizontal airflow would be obstructed.