Refrigerant charging, Commissioning data – Airedale Air Cooled Condensers R410A User Manual
Page 20

CR12
– CR105
Condensers
20
Condensers
Installation & Maintenance : 6680953 V1.2.0 02/2013
Commissioning Data
REFRIGERANT
CHARGING
It is important that the system is charged with the correct amount of refrigerant.
Remember, a seriously over or undercharged system may lead to major
component failure.
The final refrigerant charge level should be set by the design evaporating and condensing
pressures, together with a full or nearly full sight glass.
The suction and discharge pressures should be constantly monitored whilst charging is
in progress.
To calculate the system refrigeration charge, please refer to the indoor unit data.
CR12
CR16
CR22
CR30
Refrigeration
Single Circuit
Refrigerant Type
R410A
Coil Volume
l
3.0
6.0
4.7
9.3
Refrigerant Charge
(1)
kg
1.4
2.7
2.2
4.3
CR50
CR65
CR80
CR105
Refrigeration
Single Circuit
Refrigerant Type
R410A
Coil Volume
l
10.7
21.4
18.3
36.6
Refrigerant Charge
(1)
kg
4.9
9.8
8.4
16.7
(1)
For guidance only.