Electrical data, General – Airedale Air Cooled Condensers R410A User Manual
Page 15

Condensers
CR12
– CR105
Condensers
15
Installation & Maintenance : 6680953 V1.2.0 02/2013
Electrical Data
IMPORTANT
The following information is for general guidance; refer to the certified drawings
provided for installation.
CAUTION
ALL work MUST be carried out by technically trained competent personnel.
The equipment contains live electrical and moving parts, ISOLATE prior to
maintenance or repair work.
GENERAL
Once the refrigeration pipework is complete the electrical supply can be connected
by routing the cables through the appropriate casing hole and connecting the cables
as per the wiring diagram supplied with each unit
A fused and isolated electrical supply of the appropriate rating should be installed
As standard the equipment is designed for 230V, 1 Phase, 50Hz or 400V, 3 Phase, 4
wire 50Hz to all relevant IEE regulations, British standards and IEC requirements
All mains and interconnecting wiring should be carried out to National and
Local codes
Wires should be capable of carrying the maximum load current under non-fault
conditions at the stipulated voltage
Avoid large voltage drops on cable runs, particularly low voltage wiring
caution
Each unit requires an independently fused and isolated power supply.