Electrical data, Interconnecting wiring, Condensers – Airedale Air Cooled Condensers R410A User Manual
Page 16

CR12
– CR105
Condensers
16
Condensers
Installation & Maintenance : 6680953 V1.2.0 02/2013
Electrical Data
ELECTRICAL DATA
CR12
CR16
CR22
CR30
Unit Data
(1)
Nominal Run Amps
A
1.1
1.1
2.9
2.9
Maximum Start Amps
A
2.8
2.8
5.6
5.6
Recommended Mains Fuse
A
10
10
10
10
Max Mains Cable Incoming
mm²
6
6
6
6
Mains Supply
230V / 1Ph + N / 50Hz
Fan - Per Fan
Quantity
1
1
1
1
Motor Size
kW
0.24
0.24
0.63
0.63
Full Load Amps
A
1.10
1.10
2.90
2.90
Locked Rotor Amps
A
2.80
2.80
5.60
5.60
OPTIONAL EXTRAS
Short Case Axial Fan - Per Fan
Quantity
1
1
1
1
Motor Size
kW
0.61
0.61
1.4
1.4
Full Load Amps
A
2.80
2.80
6.0
6.0
Locked Rotor Amps
A
7.00
7.00
18.0
18.0
EC Condenser Fan - Per Fan
Quantity
1
1
1
1
Motor Size
kW
0.7
0.7
0.77
0.77
Full Load Amps
A
3.1
3.1
3.30
3.30
CR50
CR65
CR80
CR105
Unit Data
(1)
Nominal Run Amps
A
5.8
5.8
8.7
8.7
Maximum Start Amps
A
11.2
11.2
16.8
16.8
Recommended Mains Fuse
A
10
10
16
16
Max Mains Cable Incoming
mm²
6
6
6
6
Mains Supply
230V / 1Ph + N / 50Hz
Fan - Per Fan
Quantity
2
2
3
3
Motor Size
kW
0.63
0.63
0.63
0.63
Full Load Amps
A
2.90
2.90
2.90
2.90
Locked Rotor Amps
A
5.60
5.60
5.60
5.60
OPTIONAL EXTRAS
Short Case Axial Fan - Per Fan
Quantity
2
2
3
3
Motor Size
kW
1.4
1.4
1.4
1.4
Full Load Amps
A
6.0
6.0
6.0
6.0
Locked Rotor Amps
A
18.0
18.0
18.0
18.0
EC Condenser Fan - Per Fan
Quantity
2
2
3
3
Motor Size
kW
0.77
0.77
0.77
0.77
Full Load Amps
A
3.30
3.30
3.30
3.30
(1)
Nominal data based on 35°C ambient and a 50°C mean condensing temperature and using standard fan.
INTERCONNECTING
WIRING
CR12 - CR105
L1
Mains Incoming 230V / 1Ph + N / 50Hz
N
E