Positioning, Siting recommendations, Pipework connections – Airedale Air Cooled Condensers R410A User Manual
Page 12: Holding charge, Pipework installation - good practices, Installation data

CR12
– CR105
Condensers
12
Condensers
Installation & Maintenance : 6680953 V1.2.0 02/2013
Installation Data
POSITIONING
Unit must be positioned on an even base to ensure correct operation
Observe airflow and maintenance clearances
Where multiple units are installed, due care should be taken to avoid the discharge
air from each unit adversely affecting other units in the vicinity
When mounting the units adjacent to a wall or other vertical surface the condenser
should be positioned with the coil side facing the wall
Check all services are present and accessible
MOUNTING
Fix the condenser down using the appropriate bolt holes in unit fixing legs.
SITING RECOMMENDATIONS
Horizontal Air Discharge
Avoid where possible siting the unit where wind and air re-circulation may interfere
with the fan operation
A vertical air discharge unit is recommended for installation in windy locations or
wherever a horizontal airflow would be obstructed
PIPEWORK CONNECTIONS
CAUTION
Take care that the service connections are correctly made and in particular do not
invert the inlet and outlet connections.
PIPEWORK CONNECTIONS SIZES
CR12
CR16
CR22
CR30
Connections
Liquid Line - Sweat
in
5/8
5/8
5/8
3/4
Discharge Line - Sweat
in
5/8
5/8
5/8
3/4
CR50
CR65
CR80
CR105
Connections
Liquid Line - Sweat
in
3/4
3/4
7/8
7/8
Discharge Line - Sweat
in
1 1/8
1 1/8
1 3/8
1 3/8
HOLDING CHARGE
The units are shipped with a holding charge of inert gas to guard against contamination or
moisture during shipping and storage.
CAUTION
The charge should be checked to indicate if leaks are present prior to evacuation.
If the charge appears to be either partially or totally lost, then the unit should be
carefully checked for signs of physical damage.
PIPEWORK INSTALLATION - GOOD PRACTICES
CAUTION
The following information is based on a complete matched Airedale system
using R410A.
General
Run the refrigeration lines taking care to ensure the following:
Use straight line routes where ever possible
Refrigerant lines should be insulated in areas of high/low temperature or when
exposed to direct sunlight
When insulating refrigerant lines, cut approximately 30 - 50cm longer than the
distance between the units to ensure the insulation goes right upto the unit, leave
connections uncovered for leak testing
Remove burrs to the ends of the copper tube, holding the tube downward to avoid
allowing dirt to contaminate the tube
Avoid any contact between the discharge line and the liquid line