Dry cooler specification, General specification, Ultima water cooled chillers – Airedale Ultima Water Cooled 75kW - 450kW User Manual
Page 38: Chillers

ULTIMA WATER COOLED
Chillers
38
Chillers
Technical Manual : Part No 6259477 V1.4.0_07_2014
Dry Cooler Specification
GENERAL SPECIFICATION
Water Cooled Chiller
UWC75
UWC100
UWC125
UWC150
UWC175
Matched Dry Cooler
– Per Unit
DE75
DE100
DE125
DE150
DE175
Sound Data
Sound Pressure Level at 10m
dB(A)
52
56
56
50
56
Mechanical Data
Dimensions
Horizontal - H x L x W -
mm
1168 x 4625 x 630
1383 x 4753 x 795
1383 x 4753 x 795
1383 x 6228 x 795
2286 x 3658 x 760
Vertical - H x L x W
mm
1020 x 4625 x 1098 1335 x 4756 x 1272 1335 x 4756 x 1272 1335 x 6228 x 1272 1220 x 3658 x 2286
Weight - Machine
kg
337
388
470
646
519
Construction - Material / Colour
Painted Galvanised Steel
– Light Grey (RAL 9002)
Dry Cooler Coil
Nominal Airflow
m³/s
9.3
16.8
16.3
16.4
19.9
Discharge
Vertical or Horizontal
Fan & Motor
Quantity
4
3
3
4
6
Diameter
mm
630
800
800
800
630
Maximum Speed
rpm
870
890
890
680
1140
Connections
Water Inlet / Outlet
in
2 1/2
2 1/2
3
4
4
Electrical Data
Mains Supply
VAC
400V 3PH 50Hz
Nominal Run Amps
A
5.2
12.0
12.0
9.6
12.0
Water Cooled Chiller
UWC200
UWC225
UWC240
UWC250
UWC270
Matched Dry Cooler
– Per Unit
DE200
DE225
DE240 x 2
DE250 DE240 & DE300
Sound Data
Sound Pressure Level at 10m
dB(A)
60
59
58
59
58 & 57
Mechanical Data
Dimensions
Horizontal - H x L x W -
mm
2286 x 3658 x 760
2436 x 4783 x 878
1168 x 4625 x 630
2436 x 4783 x 878
1168 x 4625 x 630
&
1383 x 6228 x 795
Vertical
– H x L x W
mm
1220 x 3658 x 2286 1335 x 4783 x 2436 1020 x 4625 x 1098 1335 x 4783 x 2436
1020 x 4625 x 1098
&
1335 x 6228 x 1272
Weight
– Machine
Kg
601
860
391
910
391 & 611
Construction - Material / Colour
Painted Galvanised Steel
– Light Grey (RAL 9002)
Dry Cooler Coil
Nominal Airflow
m³/s
21.4
32.0
14.3
30.5
14.3 & 21.7
Discharge
Vertical or Horizontal
Fan & Motor
Quantity
6
6
4
6
4 & 4
Diameter
mm
630
800
630
800
630 & 800
Maximum Speed
Rpm
1380
890
1380
890
1380 & 890
Connections
Water Inlet / Outlet
in
4
4
2 1/2
2 x 4
2 1/2 & 3
Electrical Data
Mains Supply
VAC
400V 3PH 50Hz
Nominal Run Amps
A
18.6
24.0
12.4
24
24.0 & 16.0
(1)
Standard unit match based on 12/7°C chilled water, 40/45°C condenser glycol solution (20% ethylene), 30° ambient. For alternative
conditions, please contact Airedale.