Performance Data
All performance data is supplied in accordance with BS EN 14511-1:2013
CAPACITY DATA
Condenser Leaving/Entering Water Temperature
– based on
T of 5°C
Leaving Water
Temperature °C
25/30°C
30/35°C
35/40°C
40/45°C
Output kW
Input kW
Output kW
Input kW
Output kW
Input kW
Output kW
Input kW
UWC75
5
85.6
19.2
81.6
21.6
77.5
24.1
73.3
26.7
6
88.7
19.3
84.6
21.7
80.3
24.2
76.0
26.7
7
91.7
19.6
87.5
22.0
83.1
24.5
78.7
27.0
10
101.7
20.1
97.0
22.4
92.3
24.8
87.5
27.2
UWC100
5
116.4
25.5
111.3
28.9
105.9
32.3
100.6
35.9
6
120.6
25.6
115.2
29.0
109.7
32.5
104.2
36.0
7
124.5
25.9
118.9
29.3
113.3
32.8
107.6
36.3
10
137.1
26.3
131.1
29.8
125.0
33.2
118.9
36.7
UWC125
5
148.5
32.8
141.8
36.8
134.9
41.0
127.9
45.3
6
153.8
33.0
146.9
37.0
139.7
41.2
132.5
45.5
7
159.2
33.4
152.0
37.4
144.6
41.6
137.2
45.8
10
176.2
34.0
168.4
37.9
160.2
42.1
152.0
46.3
UWC150
5
180.3
39.3
172.3
44.2
164.1
49.2
155.7
54.4
6
186.5
39.7
178.2
44.5
169.8
49.5
161.1
54.7
7
192.7
40.2
184.2
45.0
175.5
49.9
166.6
55.0
10
212.6
41.4
203.3
46.0
194.0
50.7
184.3
55.6
UWC175
5
208.6
44.4
199.2
50.0
189.7
55.8
179.7
62.0
6
215.9
44.7
206.2
50.2
196.4
56.0
186.1
62.2
7
223.1
45.1
213.1
50.7
202.9
56.5
192.5
62.6
10
246.2
45.9
235.4
51.5
224.5
57.2
213.2
63.3
UWC200
5
237.8
49.9
227.1
56.2
216.0
62.8
204.4
69.8
6
246.3
49.9
235.2
56.2
223.7
62.9
211.8
69.9
7
254.4
50.4
242.9
56.9
231.1
63.6
219.0
70.6
10
281.0
50.6
268.7
57.1
256.1
63.9
243.1
71.1
UWC225
5
268.8
56.7
255.7
63.6
242.3
70.9
228.4
78.5
6
278.4
56.9
264.8
63.9
250.9
71.1
236.6
78.7
7
287.7
57.4
273.7
64.5
259.5
71.7
244.9
79.2
10
317.7
58.3
302.6
65.4
287.3
72.6
271.7
80.1
UWC240
5
257.0
54.8
244.9
62.2
232.4
69.9
219.8
77.8
6
266.1
55.2
253.5
62.5
240.7
70.1
227.7
77.9
7
275.2
55.6
262.2
62.9
249.0
70.4
235.6
78.2
10
303.4
57.0
289.3
64.1
275.1
71.4
260.7
78.8
UWC250
5
300.5
62.0
286.8
69.1
272.2
77.0
256.8
85.6
6
312.3
63.6
296.4
71.1
280.2
78.9
263.5
87.2
7
322.7
64.4
306.3
72.0
289.7
79.8
272.6
87.9
10
356.6
65.7
338.8
73.3
320.8
81.0
302.6
88.9
UWC270
5
300.1
63.1
285.6
71.6
270.8
80.3
255.8
89.3
6
310.6
63.4
295.7
71.9
280.5
80.6
265.0
89.6
7
321.3
63.8
305.9
72.2
290.3
80.9
274.4
89.9
10
354.3
64.8
337.7
73.3
320.9
81.9
303.9
90.8
UWC300
5
345.1
71.3
328.1
81.0
310.8
90.9
293.2
101.0
6
357.2
71.6
339.7
81.2
321.9
91.1
303.8
101.3
7
369.4
71.8
351.4
81.5
333.1
91.5
314.6
101.7
10
407.4
72.4
388.0
82.4
368.5
92.6
348.8
102.9
UWC330
5
389.8
81.0
369.5
91.5
348.9
102.4
327.9
113.6
6
403.6
81.4
382.8
91.9
361.6
102.8
340.0
114.0
7
417.6
81.8
396.1
92.4
374.4
103.2
352.3
114.4
10
461.1
83.0
437.9
93.7
414.6
104.6
391.0
115.7
UWC360
5
435.4
90.8
411.6
102.2
387.6
114.0
363.1
126.2
6
451.0
91.4
426.5
102.7
401.8
114.5
376.6
126.6
7
466.7
92.0
441.6
103.3
416.3
115.0
390.4
127.1
10
515.7
93.8
488.6
105.2
461.4
116.7
433.8
128.6
UWC400
5
477.8
102.1
453.3
115.0
428.7
128.1
403.6
141.7
6
494.8
102.7
469.6
115.5
444.3
128.6
418.4
142.2
7
512.0
103.2
486.0
116.1
460.0
129.2
433.4
142.7
10
565.5
104.8
537.3
117.8
509.3
130.9
480.7
144.4
UWC450
5
518.2
113.3
493.3
127.7
468.4
142.1
442.8
157.1
6
536.6
113.8
510.9
128.1
485.2
142.6
458.8
157.6
7
555.1
114.3
528.6
128.7
502.1
143.2
475.0
158.2
10
612.8
115.6
583.9
130.3
555.3
145.0
526.1
160.0
1
Output kW refers to the chilled water duty.
2
Input kW refers to the compressor input power.
3
Duties applicable for chilled water
T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate
5
Evaporator Water flow rate (l/s) = Output ÷ (4.19 x
T) Except Glycol use, refer to
6
Condenser Water flow rate (l/s) = (Output + Input) ÷ (4.19 x
T) Except Glycol use, refer to
7
For conditions outside those quoted, please refer to Airedale.