Technical data 47, Technical data 47 - 50, Technical data – West Control Solutions TB 45 Temperature Monitor User Manual
Page 47: 12 technical data, Inputs universal input inp1, Additional input inp2 (universal, optional)
.
12
Technical data
INPUTS
UNIVERSAL INPUT INP1
Type: single-ended, except thermocouples
Resolution:
> 14 bits
Decimal point:
0 to 3 decimals
Digital input filter:
adjustable 0,0...999,9 s
Scanning cycle:
100 ms
Linearization:
15 segments, adaptable with
BlueControl
®
Measurement value correction: 2-point or offset
Limiting frequency:
1,7 Hz
Thermocouples (Table 1)
Input resistance:
? 1 M[
Influence of source resistance: 1 úV/[
Input circuit mo
nitor
break, reversed polarity
Cold-junction compensation
w
internal,
- additional error:
typ.:
max
.:
ß_ 0,5 K
ß -2,5 K
external,
-constant reference
0...100 °C
Break monitoring
Sensor current:
1 úA
Operating sense configurable
Resistive sensors (Table 2)
Connection technique:
3-Leiter,
4-wire (not with INP2)
Lead resistance (for max. span):
max. 30 [
Input circuit monitoring:
break and short circuit
Measurement span
The BlueControl
®
software enables the internal characteristic
cu
rve for the KTY 11-6 temperature sensor to be adapted.
Divided into ranges
Physical measurement range:
0...4500 [
Current and voltage measurement (Table 3)
Span start and span:
anywhere within the
measurement range
Scaling:
freely selectable –1999...9999
Input circuit monitoring (current): 12,5% below span start (2 mA)
O
2
measurement (option)
Electromotive force measurement by means of INP1
(high-impedance mV inputs)
suitable for probes with
w
constant sensor temperature (heated probes), setting by means
of parameter
measured sensor temperature (non-heated probes),
measurement by means of INP2
ADDITIONAL INPUT INP2 (UNIVERSAL,
OPTIONAL)
Resolution:
> 14 bits
Digital input filter:
adjustable 0,0...999,9 s
Scanning cycle:
100 ms
Linearization:
as for INP1
Measurement value correction:
2-point or offset
Type:
single-ended except
thermocouples
Remaining technical data as for INP1 except:
• Voltage input ranges –10...0...+10V and -5...+5V not possible.
• Millivolt input ranges: high-impedance input for low-impedance
sources.
Technical data
TB 45
47
Thermocouple type
Measurement range
Accuracy
Typical resol.
L
Fe-CuNi (DIN)
-100...900°C
-148...1652°F
ß 2K
0,1 K
J
Fe-CuNi
-100...1200°C
-148...2192°F
ß 2K
0,1 K
K
NiCr-Ni
-100...1350°C
-148...2462°F
ß 2K
0,2 K
N
Nicrosil/Nisil
-100...1300°C
-148...2372°F
ß 2K
0,2 K
S
PtRh-Pt 10%
0...1760°C
32...3200°F
ß 2K
0,2 K
R
PtRh-Pt 13%
0...1760°C
32...3200°F
ß 2K
0,2 K
T**
Cu-CuNi
-200...400°C
-328...752°F
ß 2K
0,05 K
C
W5%Re-W26%Re
0...2315°C
32...4199°F
ß 3K
0,4 K
D
W3%Re-W25%Re
0...2315°C
32...4199°F
ß 3K
0,4 K
E
NiCr-CuNi
-100...1000°C
-148...1832°F
ß 2K
0,1 K
B*
PtRh-Pt6%
0(400)...1820°C
32(752)...3308°F
ß 3K
0,4 K
Special
-25 … +75 mV
ß 0,1%
0,01%
* Values apply from 400 °C upwards
** Values apply from –80 °C
Table 1: Thermocouple input