Dely, S.if, D.unt – West Control Solutions TB 45 Temperature Monitor User Manual
Page 38: Unit, C.del

Name
Value range Description
dELY
0...200
Response delay [ms]
µ
S.IF
Enable system interface µ
0
The system interface is de-activated.
1
The system interface is activated (field bus communication via bus coupler).
D.Unt
display unit
0
no unit
1
temperature unit
2
O2 - unit (see date
O2)
3
%
4
bar
5
mbar
6
Pa
7
kPa
8
psi
9
l
10
l/s
11
l/min
12
Ohm
13
kOhm
14
m
15
A
16
mA
17
V
18
mV
19
kg
20
g
21
t
22
Text of physical unit (definable in T.Unit/controllable via BlueControl
Ò)
O2
parameter unit for O2
µ
0
Parameter in ppm with O2 function
1
Parameter in % with O2 function
Unit
Temperature-unit
0
no unit
1
°C
2
°F
3
Kelvin
dP
decimal points
0
no decimalpoint (0 digits behind the decimal point)
1
1 digit behind the decimal point
2
2 digits behind the decimal point
3
3 digits behind the decimal point
C.dEl
0..200
Modem delay [ms]
FrEq
Switch over 50/60 Hz (only visible with BlueControl
Ò
!)
0
Netfrequency 50 Hz
1
Netfrequency 60 Hz
IExo
Block extended operating level (only visible with BlueControl
Ò
!)
0
Released
1
Blocked
IRES
LC alarm reset via the keys can be protected additionally by means of a password.
0
Enabled
1
Disabled
Pass
OFF...9999
Password (only visible with BlueControl
Ò
!)
IPar
Block parameter level (only visible with BlueControl
Ò
!)
0
Released
1
Blocked via passnumber
Configuration level
38
Configuration
TB 45