Out.0, Out.1, O.src – West Control Solutions TB 45 Temperature Monitor User Manual
Page 37: O.fai, Di.fn, Err.r, Baud, Addr, Prty
Name
Value range Description
Out.0
-1999...9999 Scaling 0% (only for Out.3 analog)
µ
Lower analog output scaling limit (corresponds to 0%). When using current or volta-
ge signals as output variables, the display values can be scaled to the output values
at parameter level. Specification of the output value of the lower scaling point is in
units of the relevant electrical quantity (mA / V).
Out.1
-1999...9999 Scaling 100% (only for Out.3 analog)
µ
Upper analog output scaling limit (corresponds to 100%). When using current or vol-
tage signals as output variables, the display can be scaled to the output values at pa-
rameter level. Specification of the output value of the upper scaling point is in units
of the relevant electrical quantity (mA / V).
O.Src
Signal source (only for Out.3 analog)
µ
0
Not active
3
Process value
7
INP1
8
INP2
µ
O.FAI
Fail behaviour
µ
0
upscale
1
downscale
Signal allocation LOGI
Name
Value range Description
di.Fn
Function of inputs
0
Direct
1
Inverse
2
Toggle key function (adjustable for 2-point operation with interface and di1)
L_r
Local / Remote switch-over
(Remote: Adjustment of values via front is blocked)
0
no function ( switching via interface is possible)
1
always on
2
di1 switches
7
limit 1 switches
8
limit 2 switches
9
limit 3 switches
Err.r
Source of control signal for resetting all stored error list entries. All error messages
and alarms are in the error list. If an alarm is still pending, i.e. unless the error cause
was removed, stored alarms cannot be acknowledged, i.e. reset. Resetting of all sto-
red error list entries.
2
di1 switches
6
Reset keys switch
Miscellaneous othr
Name
Value range Description
bAud
Baudrate of interface
µ
0
2400 Baud
1
4800 Baud
2
9600 Baud
3
19200 Baud
4
38400 Baud
Addr
1...247
Address
µ
PrtY
Parity
µ
0
No parity, 2 stop bits
1
Even parity
2
Odd parity
3
No parity, 1 stop bit
Configuration level
TB 45
Configuration